FloW CHaRt - menU
LANGUAGE
BUZZER
ON - OFF
SET DEGREES
°C- F
DISPLAY
10 - 100%
TECHNICAL
SETTINGS
SYSTEM
( PR06 = Off )
Hot WateR Kit
ConneCtion
all operations must be performed with mains power disconnected.
imPoRtant:.after.having.transported./.handled.the.WATER.CONNECTION.KIT,.check.tightness.of.all.the.compression.nuts.on.the.copper.
pipes. Take.special.care.when.connecting.the.KIT.to.the.plumbing.system.to.avoid.bending.the.copper.pipes.in.the.KIT..To.counter.the.
tightening.force.exerted.on.the.plumbing.system.connection.pipe,.use.a.wrench.or.other.tool.on.the.terminal.in.the.KIT.being.connected.
imPoRtant: after.having.connected.the.KIT.to.the.plumbing.system,.check.tightness.of.all.the.compression.nuts.on.the.copper.pipes.
tHeRmal RelieF ValVe (VST).–.SaFetY.ValVe.(VSP)
The.VSt.(Thermal.Relief.Valve).and.VSP.(Safety.Valve).valves.are.installed.in.the.plumbing.system.at.the.heating.appliance.outlet,.less.than.
one.metre.from.the.latter,.as.specified.by.the.standards.in.force.regarding.safety.devices.
oPeRation
The.controller.allows.SIMPLE.DHW.Kit.(6012014),.COMBINED.DHW.Kit.(6012015).and.
S.p.a.,.to.be.controlled..It.is.recommended.to.follow.the.wiring.connection.diagrams.of.the.flow.switch.and.pumps.to.the.controller.as.shown.
in.diagram 9, 10,
11
and 12.
It.is.recommended.to.size.the.heating.device.correctly.by.considering.the.usage.habits.of.domestic.hot.water..
If.necessary,.the.operating.thresholds.of.circulators.C1.and.C2.can.be.set.to.values.. . b elow.60.°C.and.70.°C,.respectively..It.is.recommended.to.
use.this.option.as.least.as.possible.as.particularly.cold.water.affects.the.integrity.of.the.heat.exchanger.
Activate.this.option.by.entering.the. " TECHNICAL.SETTINGS".menu,.then.accessing.the. " PRODUCT.TYPE".menu,.entering.code. " 33".and.selecting.
the.PR07.=.2.value..Therefore,.the.threshold.adjustment.range.of.the.pumps.allows.the.temperature.to.be.decreased.to.10.°C.(only.valid.for.
DHW.kits).
ITALIANO
ENGLISH
FRANCAIS
ESPANOL
DEUTSH
SETTINGS FACTORY
CODE 44
TEST OUT 1
TEST OUTPUTS
TEST OUT 2
TEST OUT 3
I1= xx°C
Heating device
(
STATUS Stove
I2= xx°C
I3= xx°C
I4= On / Off
PR06
PRODUCT
CODE 33
PR08 BOILER (On / Off )
PR09 SET BOILER Max
( 47 - 70°C )
PR10 SET BOILER Min
( 30 - 46°C )
PR11 PUFFER ( On / Off
)
PR12 thermal differential to PUFFER On (5 - 12°C) Default = 7°C
PR13 thermal differential to PUFFER Off (3 - 8°C)
engliSH
PR01 CIRCULATOR 1 Threshold OUT 1 (55- 65°C)
Default = Heating device 60°C
PR02 CIRCULATOR 1 Delta OUT 1
(1 - 5°C)
PR03 CIRCULATOR 2 Threshold OUT 2 (65 - 75°C)
Default = Heating device 70°C
PR04 CIRCULATOR 2 Delta OUT 2
(1 - 5°C) Default = 5°C
probe)
PR05 ANTIFREEZE Threshold
PUFFER
(
probe)
(2 - 10°C)
BOILER
(
probe)
(Flow switch)
0 = Heating device DSA
1 = All Inclusive
2 = WATER CONNECTION KIT
Default = 60°C
Default = 30°C
Default = 5°C
SEPARATOR
.Kit.(6012021).,.supplied.by. noRDiCa
Default = 5°C
Default = 5°C