* When selecting the logic operator, ensure that the resulting function fulfils the
specified safety function and corresponds to the specified properties.
Control outputs 1-4
Input
 Safety input 1
 Safety input 2
 Safety input 3
 Safety input 4
 BTR*
 ERROR
 as for safety output 1
 as for safety output 2
 as for safety output 3
 as for safety output 4
* The control output is switched on after initialization.
No input is assigned when selecting BTR, error or safety output. The outputs'
switch-on/switch-off delay time of between 0.0 s and 99.9 s can be set in
0.1 second steps.
LED displays
1
2
LED 1
LED 2
3
4
5
6
LED 3
LED 4
7
8
9
10
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
Operating time
The operating time is the maximum time permitted on a sensor between actua-
tion of both sensor contacts.
With 2-hand operation, it is the maximum time permitted between actuation of
both sensors.
Safe condition
The safety outputs are opened or with high resistance.
Hazardous condition
The safety outputs are closed or with low resistance.
8

Technical specifications

See "Technical specifications" from page
9

Installation

Danger of electrocution!
Ensure that the safety control unit is installed and put into
operation only by specially trained, authorized personnel.
Danger
- Installation of the safety control unit is only permitted in a voltage-free state.
- Ensure that the prescribed fuses
- Snap the safety control unit onto a mounting rail (DIN EN 60715 TH35) in the
switch cabinet. The safety control unit is fixed.
- Connect the safety control unit.
The pluggable terminal blocks can be coded by means of pins, the sockets
in the device are inversely coded by means of coding tabs.
Art.-Nr./Art. No./Réf./N° art/N° art.: 9010008B01M
Logic
Switch-on/switch-off
delay in s
 AND
 OR
, s
 NAND
 NOR
 XOR
 XNOR
 NOT
, s
Operability ("Ready")
Fault ("Error")
Safety input 1 ("I 1")
Safety input 2 ("I 2")
Safety input 3 ("I 3")
Safety input 4 ("I 4")
Safety output 1 ("O 1")
Safety output 2 ("O 2")
Safety output 3 ("O 3")
Safety output 4 ("O 4")
15.
(see "Technical
specifications") are used.
Version/Version/Version/Versione/Versión: 1.3
t
ON
___
- If the safety input remains free:
Ensure that the contact makers of this safety input are bridged.
t
OFF

10 Electrical connection

- Electrical connection is only permitted in a voltage-free state.
- Make sure that the details described in the technical specifications are al-
ways complied with.
- Measures to improve the equipment's immunity to interference from line-
conducted and radiated high frequency interference are to be taken
(DIN EN 60204-1:2007-06, para 4.4.2).
When connecting the sensor, the sensor power supply voltage (+) and (-)
terminals identified in the technical specifications are to be used.
Terminal connections
Components
Safety input 1
Safety input 2
Safety input 3
Safety input 4
Safety output 1
Safety output 2
Safety output 3
Safety output 4
External contactor/
Start 1-2
Operating voltage
Control output 1
Control output 2
Control output 3
Control output 4

11 Commissioning

Danger
In random order:
- Damp safety sensors.
- Apply operating voltage.
- Then actuate the start button if necessary.
The LEDs of the inputs and outputs used and the "Ready" LED light up.
The safety control unit is ready. The safety control unit switches through the
safety output.
Accessories
Spring terminals are supplied as standard (order number
878598).
Optional screw terminals (order number 878719) and dou-
ble terminals (order number 878717) are available from
elobau.
A corresponding coding tab set is available from elobau un-
der order number 350SAE001.
Terminals Explanation
5-8
Depending on configuration, the inputs at
terminals 5, 13, 21, 29 (+) or (-) are read-
13-16
only.
21-24
Connection options:
29-32
- Sensors with 2-NO system
- Sensors with NO/NC System
- Emergency stop push button
- 2-hand control
- Light grid (OSSD)
- Photoelectric sensor (OSSD)
Switching dependent on
1, 25
- Safety input 1-4
- Logic
2, 26
- Switch-on/switch-off delay (optional)
3, 27
- Contactor/start inputs (optional)
4, 28
11, 12
External contactor and/or start button
(automatic, manual or monitored)
9, 10
17
Not suitable for safety functions!
Switching dependent on
18
- Safety input 1-4
19
- Logic
20
- Switch-on/switch-off delay times
(optional)
Danger of electrocution!
Ensure that the safety control unit is installed and put into
operation only by specially trained, authorized personnel.
NOTE
Make sure that no external voltage is applied to the safety
inputs when the operating voltage is applied (e.g. by devic-
es with OSSD outputs).
Datum/Date/Date/Data/Fecha: 29.08.2017
5/18

Publicidad

Tabla de contenido
loading

Tabla de contenido