Compressor Stop-Start Delay Parameter ( Default = 0) MODBUS ADRES:40010
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes
Compressor Start-Start Delay Parameter
This time delay must be expired between two activation of the compressor. It can be
adjusted from 0 to 20 minutes.
Sensor Defect Parameter ( Default = 0 ) MODBUS ADRES:40012
Compressor is active during this time period in case of probe defect (Default = 0)
MODBUS ADRES:40013
If probe defect parameter
from 0 to 99 minutes.
Compressor is inactive during this time period in case of probe defect
( Default = 0 )MODBUS ADRES:40014
If probe defect parameter
from 0 to 99 minutes.
Buzzer Function Selection Parameter
Buzzer is active during this time
If buzzer function selection parameter value
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
When this parameter is 1, if decrement button is pressed,
condition buzzer is active till buzzer silence button is pressed.
Communication Mode Selection Parameter
Slave ID Parameter
Device communication address parameter (1 to 247).
Programming Section Accessing Password
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is
selected 0, password will not be asked
i
,
is selected "Cooling". If operation type is selected "Heating " ,skip to the
6.2 Modbus Adresses of Device Status Parameters (Read Input Register)
MODBUS ADDRESS:30001
MODBUS ADDRESS:30002
MODBUS ADDRESS:30003
A
A
MODBUS ADDRESS:30004
A
MODBUS ADDRESS:30005
MODBUS ADDRESS:30006
Compressor is OFF in case of sensor defect.
Compressor is ON in case of sensor defect.
Compressor operates periodically according to
case of sensor defect.
Buzzer is inactive.
Buzzer is active during sensor failures.
PROKEY communication selected.
Rs485 communication selected.
( Default = 1 ) MODBUS ADDRESS=40018
,
,
,
Temperature Value
Reserved
Led Status
Device Status : 1.bit Buzzer Status
Output Status
Device Type and Device Version
( Default = 0) MODBUS ADRES:40011
is 2, then this parameter is observed. It can be adjusted
is 2, then this parameter is observed. It can be adjusted
( Default = 0 ) MODBUS ADDRESS:40015
( Default =
) MODBUS ADDRESS:40016
=0, this parameter can not be
( Default = 0 ) MODBUS ADDRESS:40017
( Default = 0 ) MODBUS ADDRESS:40019
.
and
Parameters are observed if Operation type
o
: 0.bit C Led,
6.bit Compressor Led,
13.bit Program Led, 14.bit Set Led
2.bit Sensor Lost Status
and
Time periods in
is observed. In this
parameter
10