Smoke alarms must always be
installed at the ceiling and in the
centre of the room as possible,
however, with a minimum
clearance of 0.5 m to walls, beams
Where?
How high?
Observe national regulations and guidelines.
10
at the ceiling
up to 6 m
room height
or furniture. Each smoke alarm
enables monitoring of a maximum
floor space of 60 m².
Where exactly?
at least 0.5 m
Centre of ceiling
How much floor space?
(View from top)
up to 60 m