Found on LCII Only
See accessory instructions for more information
- Install the sensor with "grid" exposed.
- Do Not use rain sensor if the control is being used as a smoke
vent.
- Wire with 22 AWG - 2 conductor shielded, twisted pair
50 ft (15m) Max. Note:Connect shield to "G" (ground)
- Consider prevailing winds when locating
the sensor. Keeping away from obstructions.
- The sensor can be mounted outside (maximum sensitivity)
or inside vent edge (minimum maintenance)
R
h
* See Step #9 "Testing"
Wire leads may be reversed.
Total distance
re Size
transformer to
ass II)
farthest window
50 ft (15m)Max.
8 AWG
4 AWG
100 ft (30m)Max.
2 AWG
150 ft (60m)Max.
anded Wire recommended.
Refer to Class II codes.
25 VAC
oltage)
Rain Sensor Guidelines
#3
M
3
2
1
C
(Without Locks)
#2
M
OR (With Powered Locks)
7
#1
M
Screen Interlock
on each motor
(See Step #5)
Lock #2
Lock #1
M