991h/01
EC0020 series manual call points are certified and approved according to EN54-11 -
Manual callpoints and EN54-17 - Short-circuit isolators.
EC0020 manual call points are specially designed to operate with
INIM Electronics analogue addressable fire-control panels.
The trigger element and device status LED are located in the front
case of the device.
LED
Red
Yellow
Flashing: Manual callpoint ready and
Green
On solid: Manual callpoint activated by
In the event of short-circuit between the two connection wires and
the control panel (loop), the built-in isolator shuts off the negative
current and isolates the section involved. For further details
regarding the isolator, refer to the "ILP Specification" datasheet.
Details regarding the EC0020 manual callpoint, its unique serial
number and information regarding the loop terminal connections
can be found on the label inside the device housing.
The device package contains two fork-end keys which can be used
to open the housing and reset the device.
The flush-mount backbox and protective front plate are accessory
items and must be purchased separately.
TECHNICAL SPECIFICATIONS
Operating voltage
Current draw in standby
Current draw in alarm
Operating temperature
Humidity (without condensation)
Dimensions (HxWxD)
Weight
The EC0020 manual callpoint uses a simple mechanism which
consists of a rigid plastic operating element and an over-center
spring mechanism. Pressing on the black spot simulates "Break
Glass" activation and triggers an alarm.
Activation is signalled by a yellow and black striped flag which
drops into view on the upper part of the frontplate and a solid red
visual signal on the LED indicator.
The EC0020 manual call point is reset by inserting the key
provided into the key slot and by pushing the trigger mechanism
upwards as far as possible, after which the key must be turned
clockwise until the mechanism locks back into position.
EC0020
Addressable resettable manual callpoint
Meaning of visual signals
Manual callpoint activated
Short-circuit on loop
operating properly
the control panel
19-30 Vdc
Max 80 A @ 24V
5 mA @27.6V
-10°C / +55°C
95% RH
84 x 84 x 45 mm
Activation
Reset
Description
A
126 g
F
K
B
D
J
I
G
E
H
A
Callpoint button - rear
B
Details label
C
Removable serial number stickers
D
Terminals
Backbox with fixing screw holes and
E
cable entry
F
Fixed back-locking clips
G
Fixed back-locking clip positions
H
Back-locking backbox clips
I
Back-locking clip positions
J
Reset key slot
K
Protection front plate clips
0832
0832-CPR-F0443
ATTENTION!
F
K
C
G
3