6.3

SCHEME 3

Low - heating circuit (1) and high temperature - heating circuit (2) zones with room thermostat
1
External sensor - terminal block M2 (4-5) on the boiler
2
Low temperature zone mixing valve (QX21-N-QX22)
3
Low temperature circuit pump (QX23-N)
4
Low temperature circuit probe (BX21-M)
5
Low temperature circuit safety thermostat (connect in series to the zone pump, see chap. 8.3)
6
Low temperature zone room thermostat input (12V) (H2-M)
7
Electrovalve or externally powered high temperature zone pump
8
High temperature zone ambient thermostat (for connection see chapter 8.1)
Enter menu 2 from the Remote Control, as described in section 5, and make the following settings:
PROGRAMME
MENU
ROW
5715
5977
CONFIGURATION
6020
6046
Access menu 3
834
HEATING CIRCUIT 1
Connect the low temperature zone protection thermostat in series to pump 3.
7104900.03 (1-11/13)
PARAMETER
Heating circuit 2
H5 input function
Function of extension module 1
Function of H2 input on module 1
Actuator stroke time:
26
VALUE TO SET
On
Heating circuit 2 enable
Room
Circuit 2 thermostat enable
thermostat CH2
(terminal block M1 (1-2) on boiler)
Temps / mode
Low temperature zone enable
CH1
Room
H2 input enabled as low temperature zone
thermostat CH1
Default 180 s
Mixing valve close time
DESCRIPTION
room thermostat