Ensure that the equipment plugged into the four battery power-supplied/surge outlets
2.
does not exceed the UPS unit's rated capacity (1000VA/600W for OR1000ERM1U,
1500VA
/900W for OR1500ERM1U). If the rated unit capacities are exceeded, an overload
condition may occur and cause the UPS unit to shut down and the circuit breaker to
trip.
If the power requirements of your equipment are listed in units other than Volt-Amps
3.
(VA), convert Watts (W) or Amps (A) into VA by performing the calculations below.
Note: The equation listed below only calculates the maximum amount of VA that the
equipment can use, not what is typically used by the equipment at given time. Users
should expect usage requirements to be approximately 60% of the maximum power
requirements:
Watts (W) x 1.67 =VA or Amps (A) x 230 = VA
Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate
the approximate requirements.
There are many factors that can affect the amount of power that your computer system
will require. The total load that you will be placing on the battery-powered outlets
should not exceed 80% of the unit's capacity.
DESCRIPTION
LCD module display
1.
LCD shows all the UPS information with icons and messages.
Power on LED
2.
This LED is illuminated when the utility condition is normal and the UPS outlets
are providing power, free of surges and spikes.
Power Switch
3.
Master on/off switch for equipment connected to the battery power supplied outlets.
LCD function selected switch
4.
The switch can be used to select the LCD display contents Including input/output
voltage and estimated run time, etc.
Battery, Surge and AVR Outlets
5.
Provides four battery power, surge protected and AVR outlets for connected equipment
and ensures temporary uninterrupted operation of your equipment during a power failure.
Surge Outlets
6.
Provides two surge protected outlets for connected equipment.
Expansion Port
7.
Allows users to add the optional SNMP card.
Communication Protection Ports
8.
Communication protection ports will protect any standard modem, fax, telephone line,
broadband network or Ethernet connection.
BASIC OPERATION
1
2
3
5
6
4
NETWORK
OUT
IN
8
7
Push To
RESET
AC INPUT
USB
SERIAL
9
10
11
12