programmed threshold (programmed as described for the model ID200). Furthermore, in the event of a rise in
temperature within the protected environment, the sensibility of the smoke chamber will be increased. This operating
mode, characterized by high sensitivity, allows detection of fires which produce a large amount of flames but low smoke
emission (e.g. combustion of alcohol or similar highly-inflammable products).
• "OR"; the detector signals alarm status when smoke in the protected environment exceeds the programmed threshold
(programmed as described for the ID100 model) or when the temperature within the protected environment exceeds the
programmed threshold (programmed as described for the ID200 model). This operating mode, characterized by a medium-
high sensitivity, allows detection of fires which generate a substantial amount of smoke (slow burning fires) and also fires
which generate high temperatures with low smoke emission (chemical products).
• "AND"; the detector signals alarm status when the smoke and temperature in the protected environment exceed the
programmed thresholds simultaneously (programmed as described for the ID100 model and ID200 respectively). This
operating mode, characterized by a low sensitivity, lowers the false alarm rate and is useful in applications where either the
smoke or heat values in the protected environment may increase without the risk of fire.
Given the limited response, consider the conditions in the protected environment
carefully before selecting this operating mode.
• "SMOKE"; the detector assumes the characteristics of the ID100 model
• "HEAT"; the detector assumes the characteristics of the ID200 model
Technical specifications
Power supply
Average current draw in standby
Average current draw in alarm
Current draw by the "R" output
(internally limited)
Operating temperature
Humidity (without condensation)
Height (standard base included)
Diameter (standard base included)
Weight (standard base included)
Weight (without base)
The detectors are supplied with protective covers which help to protect them against
minor damage and dust contamination which may occur during the installation phase.
The covers should not be removed until the system is ready to start up.
Iris series detectors should be used with one of the following compatible mounting bases:
• EB0010; standard base
An example of installation using standard bases is shown opposite.
The value of the EOL resistance depends on the type of control panel in use.
• EB0020; relay base
Appropriate when the detector is to be connected to an intrusion control panel or to a control panel using 4 wires. For the
respective wiring instructions, refer to the leaflet supplied with the EB0020.
The two removable serial-number stickers should be taken off and one should be
attached to the mounting base and the other to the installation layout.
Once the base is located properly in its placement, place the detector unit onto the base and, with minimum
force, turn it clockwise until notch [A] aligns with notch [B] (in order to attach the detector to the base); turn it
still further until notch [A] aligns with notch [C] (in order to allow the base to engage with the detector contacts).
After installation and during periodic maintenance inspections, you must carry out the following operations on
each detector:
• Check the LED; if the LED blinks at 5 second intervals, the detector is in fault status. This may be due to dust
contamination. If after cleaning, this condition persists, remove the faulty detector and replace it with a new one. The
EITK-DRV driver will assist you in finding the cause of faults.
• Optical smoke detector test; smoke detectors should be tested immediately after installation and periodically during
maintenance inspections in accordance with the established standard regulations and codes in force. To test smoke
detectors, use an approved test aerosol strictly in accordance with the accompanying instructions.
Ensure that the smoke inlet ports to the smoke detection chamber are not blocked. Check the contamination level of the
smoke detection chamber via the EITK-DRV. If the contamination level is high, detach the detector from its mounting base
6
ID100
10-30V
90 A
Max 40mA
Max 14mA
-5°C / +40°C
46mm
Installation
Testing and maintenance
ID200
ID300
70 A
90 A
95% RH
54mm
110mm
160g
91g