and open the chamber then, using a small, soft-bristle brush or hand-held vacuum cleaner remove all dust particles from
inside and around the smoke detection chamber and free the protection mesh from all contaminants.
• Heat detector test; using a suitable device (e.g. hairdryer), create heat in the vicinity of the detector, then work through
the steps described in the device instruction sheet. During each periodic maintenance inspection, ensure that the heat
element is intact and that is not obstructed by dust or paint. If it is, using a small, soft-bristle brush or hand-held vacuum
cleaner remove all contaminants.
The bicolour LED (360° viewing) indicates the detector status.
• Green blinking at 30-second intervals: detector in standby status (i.e. operating properly).
• Green blinking at 5-second intervals: detector in fault status. Further details regarding the cause of the fault (high
contamination level in the smoke chamber, detector component fault, etc.) can be obtained through the EITK-DRV driver.
• Red LED On solid: detector in alarm status.
The detectors have an output (terminal "R"), for the connection of an alarm repeater LED. This LED will activate
when the detector it refers to triggers an alarm.
The EITK-DRV driver allows you to change the operating parameters of the detectors, check the contamination
level of the smoke chambers and also obtain accurate diagnostic data. It can operate through the USB port of a
computer furnished with the relative software programme, or can function autonomously by way of the battery
housed inside.
Each detector is capable of retaining memory (smoke and/or temperature depending on the model) of the 5
minutes prior to an alarm. Therefore, if an alarm occurs, it will be possible to obtain information regarding the
onset of the fire by simply connecting the EITK-DRV driver to the detection line.
For further information and details regarding use of the EITK-DRV driver, refer to the respective handbook.
Iris series detectors must be used exclusively with fully compliant, compatible control panels. Detectors may not
provide timely warning of fire if coverage is limited by large obstructions (pillars, large machinery, etc.). When
installing or working on a fire detection system, always refer to and comply with the established standard
regulations and codes. Appropriate fire-risk assessment should be undertaken to determine the type of detectors
required and their placements.
DoP, EC DoC and certificates related to these products can be downloaded from the following link:
www.inim.biz/certifications
Conventional optical smoke detector for fire detection and fire
alarm systems installed in buildings
INIM Electronics reserves the right to change
the technical specifications of this product
without prior notice.
8
Operating mode
Using the EITK-DRV driver
Warnings and limitations
CE marking and certifications
Conventional class P heat detector for fire detection and fire
alarm systems installed in buildings