G e n e r a l i n f o r m a t i o n :
The AMI/MIA/CIA series of Moisture Indicators are
designed to monitor the moisture content within the
liquid line of a Refrigeration system. When the liquid
line is empty, circles may be seen in the glass (only
AMI). However, when the liquid refrigerant touches
the glass, the circles disappear indicating the system is
fully charged.
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure
to comply can result in device failure, system
damage or personal injury.
• According to EN 13313 it is intended for use by
persons having the appropriate knowledge and
skill.
• Ensure that the system is correctly labeled with
applied refrigerant type and a warning for
explosion risk.
• Before opening any system make sure pressure in
system is brought to and remains at atmospheric
pressure.
• Do
not release any
refrigerant into the
atmosphere!
• Do not exceed the specified maximum ratings for
pressure and temperature.
• Do not use any other fluid media without prior
approval of EMERSON. Use of fluids not listed
could result in: Change of hazard category of
product and consequently change of conformity
assessment
requirement
accordance with European pressure equipment
directive 2014/68/EU.
• Ensure that design, installation and operation are
according
to
European
standards/regulations.
M o u n t i n g l o c a t i o n :
• AMI/MIA/CIA has to be installed only in the liquid
line, otherwise the humidity reading can show wrong
values.
• AMI/MIA/CIA is bi-directional and may be installed
in any position which allows visual access to the
indicator window itself.
• The Moisture indicator is normally located after the
filter drier and before the solenoid valve.
Fig. 2
Color Code CIA
Refrigerants
(°C)*
Blue/ Dry
Purple
Fuchsia/ Caution
Rose/Caution WET!
Note: *) Liquid temperature
Color Code AMI/MIA
Refrigerants
(°C)*
Blue/
Dry
Purple
Fuchsia/
Caution
Rose/
Caution WET!
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Moisture Indicator
Series AMI / MIA / CIA
I n s t a l l a t i o n :
• Do not remove seal caps until ready for installation
in order to minimize entering of moisture and dirt.
• Avoid damaging the connections!
B r a z i n g :
• The lens assembly on AMI "SS" models should be
removed before brazing. Do not exceed 8 Nm
(70 inch lbs) when reassembling to avoid damaging
the O- ring seal.
• The MIA/CIA are fully hermetic and cannot be
disassembled.
• Perform and consider the brazing joint as per
EN 14324.
• Before and after brazing clean tubing and brazing
joints.
• Minimize vibrations in the piping lines by
appropriate solutions.
• To avoid oxidization, it is advised to purge the
system with an inert gas such as nitrogen while
brazing.
• Do not exceed the max. body temperature of +100°C!
• To avoid overheating it is advised to make the joint
at one end cool the device completely before
repeating the procedure on the other end connection.
for
product
in
Fig.1
P r e s s u r e T e s t :
After completion of installation, a pressure test must be
and
national
carried out as follows:
- according to EN 378 for systems which must
comply with European pressure equipment
directive 2014/68/EU.
- to maximum working pressure of system for other
applications.
Warning:
• Failure to do so could result in loss of refrigerant
and personal injury.
• The pressure test must be conducted by skilled
persons with due respect regarding the danger
related to pressure.
-40
-20
3
6
5
10
10
20
16
32
R404A
R22
R134a
R507
25
25
15
38
35
25
52
50
45
25
40
33
38
65
50
52
90
60
25
80
60
38
130
110
52
185
140
25
145
120
38
205
150
52
290
180
www.climate.emerson.com/en-gb
Operating instructions
A1 (CIA only)
R744
-10
0
+5
8
11
13
14
19
22
29
39
46
46
63
75
A1 (AMI /MIA)
R407C
R410A
20
26
30
35
40
55
50
64
75
35
42
50
55
68
85
85
109
120
90
94
110
120
144
190
150
230
270
130
151
165
160
232
290
190
371
420
AMI_MIA_CIA_OI_EN_DE_FR_ES_IT_RU_1120_R12_862604.docx
L e a k a g e T e s t :
Conduct a tightness test according to EN 378-2 with
appropriate equipment and method to identify leakages
of external joints. The allowable leakage rate must be
according system manufacturer's specification.
H u m i d i t y R e a d i n g :
• The humidity content in mg Water per kg refrigerant
(ppm) can be identified by the color code in Fig.2.
• A minimum period of 12 hours is recommended after
installation before attempting to determine system
moisture content
• In case of indicator is showing fuchsia or rose color
the change of the Filter-Drier is required.
S e r v i c e / M a i n t e n a n c e :
Disconnect electrical power before service.
• Fully depressurize AMI/MIA/CIA. After reducing
pressure to atmospheric the AMI may be opened and
internal parts removed and replaced. In case of repair
work or replacing the lens assembly on AMI always
use new gaskets.
• Defective MIA/CIA must be replaced, they cannot be
repaired.
T e c h n i c a l D a t a :
Maximum allowable working pressure PS
AMI: 35 bar
Test pressure PT
AMI: 39 bar
Medium Temperature
Fluid group (acc.PED)
Standards
Medium compatibility
A1:
AMI/MIA:
R134a, R22, R404A, R507, R407C,
R513A
MIA only:
R410A
CIA only:
R744
A2L:
MIA only:
R452B, R454A, R454B, R454C,
R123yf
CIA only:
R32
Markings
UL (SA 4876),
CSA (except AMI-3, MIA-078),
MIA > 25 mm)
+20
25
20
6
34
9
72
21
116
34
A2L (MIA only)
R513A
R452B
R454B
15
22
24
20
34
34
24
46
46
19
28
28
25
42
42
30
58
58
44
66
68
58
99
101
71
136
138
75
112
119
98
168
170
121
230
232
MIA: 45 bar
CIA: 60 bar
MIA: 49.5 bar
CIA: 66 bar
-40...+100 °C
I (A2L) + II (A1)
EN 12 178
(acc. Cat. I PED - AMI >32mm,
A2L (CIA only)
R32
38
52
8
12
13
19
29
43
46
69
R454A
R454C
R123yf
22
22
12
30
28
14
38
35
16
27
27
14
37
35
17
48
44
20
64
64
34
87
82
40
122
105
46
108
108
58
148
138
68
190
177
78
Date: 02.11.2020

Publicidad

loading

Resumen de contenidos para Emerson AMI Serie

  • Página 1 MIA: 45 bar CIA: 60 bar • Do not use any other fluid media without prior Test pressure PT approval of EMERSON. Use of fluids not listed AMI: 39 bar MIA: 49.5 bar CIA: 66 bar could result in: Change of hazard category of Medium Temperature -40…+100 °C...
  • Página 2 T e c h n i s c h e D a t e n : • Nach dem Einlöten des ersten Anschlusses Bauteil • Es dürfen nur von EMERSON freigegebene Max. zulässiger Betriebsdruck PS ganz abkühlen lassen, dann zweiten Anschluss Medien eingesetzt werden.
  • Página 3 I n f o r m a t i o n s t e c h n i q u e s : • Ne pas utiliser un autre fluide que ceux indiqués Pression maximale autorisée PS sans l’approbation obligatoire d’EMERSON. AMI: 35 bar MIA: 45 bar CIA: 60 bar L'utilisation d'un fluide non approuvé...
  • Página 4 • No use ningún fluido que no haya sido D a t o s T é c n i c o s : previamente aprobado por EMERSON. El uso de Máx. presión permitida PS sustancias no aprobadas puede dar lugar a un...
  • Página 5: Istruzioni Operative

    Refrigerante R404A R134a R407C R410A R513A R452B R454B R454A R454C R123yf R507 (°C)* Azzurro / secco viola Fucsia/ Attenzione Rosa / Attenzione – umido Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 02.11.2020 Am Borsigturm 31 I 13507 Berlin I Germany AMI_MIA_CIA_OI_EN_DE_FR_ES_IT_RU_1120_R12_862604.docx...
  • Página 6 A2L (MIA только) Refrigerants AMI/MIA R404A R134a R407C R410A R513A R452B R454B R454A R454C R123yf R507 (°C)* Сухо / синий фиолетовый Внимание/ бордовый Влага/ розовый Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 02.11.2020 Am Borsigturm 31 I 13507 Berlin I Germany AMI_MIA_CIA_OI_EN_DE_FR_ES_IT_RU_1120_R12_862604.docx...

Este manual también es adecuado para:

Mia serieCia serie