5.1 Warnings and error messages during operation
Key
A0000
GB
A0001
A0002
A0004
A0008
A0010
A0020
A0080
A0100
A0400
A4000
98
The code displayed via parameter Warnings 269 can be composed
of several messages. Key A0088 signals warnings A0008 + A0080,
for example.

Warning messages

No warning present.
Frequency inverter overloaded, warning code (A0002 or A0004)
Frequency inverter overload (60 s). Check load behavior.
Short-term overload (1 s). Check motor and application parameters.
Max. heat sink temperature reached, check cooling system and fan.
Max. interior temperature reached, check cooling system and fan.
Speed set point is limited by a controller.
Max. motor temperature reached, check motor and sensor.
Mains phase failure, check mains fuses and supply cable.
Limit frequency reached; output frequency is limited.
DC link voltage has reached the Type-specific minimum.