Electronic build in transformers for low-voltage halogen lamps
Protection Class II, CE
All data refer to the 230V-240V~ model unless specified otherwise
1.Technical Data:
Type
Nominal voltage
Nominal current at 230V
Power range
Open circuit safety
Output voltage
Short-circuit and overload protection
Starting
Ambient temperature ta
Case temperature tc-point
Excess temperature cut-off
Standards
EMV conformity
Primary main
Sekundary main
Dimmer types
Diameter of wires
Cable
(Terminals)
Bared wire end
2. Installation Instructions
The installation may only be carried out by an electrical specialist in accordance with international and national
standards. The devices are designed for the use with LV halogen lamps only. When working on electrical systems, the
protection against electric shock is to be ensured by disconnecting the system. Instal primary and secondary mains
intersection-free (radioshielding). The tc temperature may not be exceeded. The devices do not contain serviceable
components and may not be opened.
3. Important Information
Our transformers are surge-voltage-stable up to values above those prescribed by the respective standards. As a
protection against high voltage surges, as they occur e.g. when switching fluorescent lamps and discharge lamps with an
inductive ballast, motors (fans, etc.) and other inductive charges, the load circuits for devices of this kind are to be clearly
separated from each other.
4. Safety Function
In case of a short circuit or overload the electronic transformer will automatically cut off. It does not have a protection of
the conventional kind. Thus the load circuit is not separated!
As soon as the defect has been repaired, the transformer will automatically cut back in.
5. Excess Temperature
In case of excess temperature through external heat sources or inpermissible covers the built-in temperature switch
disconnects the transformer from the mains (Types TL105, TL150, TL150S, TL210, TL210S), for the other types the
build-in over temperature control will reduce power. As soon as the transformer has cooled off, it will automatically cut
back in.
Description and Installation Procedure
461067
60VA
0,26A
60VA
10-60VA
Lamp-sparing soft start, thus no current peaks when the device is swiched on
Max.70°C
461157, 461217 with automatic cut-off through built-in temerature switch,
EN 61547, EN 55015, EN 61000-3-2, EN 61000-3-3
Gira Universaldimmer 50-200W, Order-No.: 031000
Gira Tronic-Dimmer 20-525 VA, Order-No.: 030700
PRI
SEC
PRI
SEC
461107
230-240V~, +6% -10%, 50/60Hz
105VA
0,46A
105VA
20-105VA
guaranteed
11,5V RMS
Electronic cut-off with automatic restart
-20° - +50°C
Max.80°C
otherwise controlling back of power
EN 61347, EN 61047
Min. H03VV-F 2x0,75 mm², for pull relief
Min. H03VV-F 2x0,75 mm², max. 2m long
techn. status of dimmers July 2002
0,75 – 1,5mm²
AWG 20-16
6mm
461157
461217
150VA
210VA
0,65A
0,92A
150VA
210VA
20-150VA
50-210VA
Max.85°C
Max.75°C