Addressing the BUS and setting its speed via dip
switch
The device address must be unique and can only be programmed
using dip switches.
Note that the standard speed of the bus for VEDO control panels is
38400 baud.
No.
DIP1
DIP2
DIP3
1
OFF
OFF
OFF
2
ON
OFF
OFF
3
OFF
ON
OFF
4
ON
ON
OFF
5
OFF
OFF
ON
6
ON
OFF
ON
7
OFF
ON
ON
8
ON
ON
ON
Terminal block description
Earth
Earth connection terminal
BUS IN
V+
485 communication BUS power supply input positive
V-
485 communication BUS power supply input negative
A
RS485 data BUS for connection to the control panel (IN) - A
B
RS485 data BUS for connection to the control panel (IN) - B
BUS OUT
V+
Power supply positive output. 485 communication bus.Limited to 1.5A
V-
Power supply negative - output reference. 485 communication
BUS power supply
A
RS485 data BUS for connection to other devices (OUT) - A
B
RS485 data BUS for connection to other devices (OUT) - B
OUTPUTS POWER SUPPLY
V+AUX1
Auxiliary 1 power supply output positive. Limited to 1.5A
V-
Auxiliary 1 power supply output negative
V+AUX2
Auxiliary 2 power supply output positive. Limited to 1.5A
V-
Auxiliary 2 power supply output negative
24H
Tamper contact input
OUTPUTS
O1
Open collector output 1. Programmed as module Anti-Sabotage
by default. The output is active when module sabotage occurs.
O2
Open collector output 2. Programmed as module Low Battery
Anomaly by default. The output is active when the programmed
time has elapsed since the moment at which the battery was no
longer detected or the voltage at its terminals is 10.7 Vdc or 15 Vdc.
O3
Open collector output O3. Programmed as module No 230V
Mains Anomaly by default. The output is active when the
programmed time has elapsed since the moment at which the
network was no longer detected.
Confi guration jumpers
JP1
RS485 output termination*
JP2
RS485 input termination*.
* Always remember to insert an end-of-line resistor between A and B
of the 485 connection (using the relevant jumpers) to the two ends
of the main BUS line.
LED signals
DL1
Flashing slowly: no data transfer over BUS at the speed set
using the dip switch.
Flashing quickly: data transfer over BUS in progress.
DL2
Off: the peripheral is communicating correctly.
Very slow fl ashing: (approx. 3 seconds) no data package on
the BUS.
DL3
On: indicates that one of the Open Collector outputs is under
protection due to a short circuit.
6
DIP4
DIP5
DIP6
not
used
BAUD
DIP7
DIP8
9600
OFF
OFF
38400
ON
OFF
(default)
57600
OFF
ON
115200
ON
ON
PSU connector
J1
External 230 V - 50 Hz power supply unit connector
Tamper contact connection
The 24H terminal needs the Tamper
contact to be connected in single
balanced confi guration.
A resistance of 1.8KΩ, in series with
the contact, is required.
Connecting V- reference terminal
The incoming RS485 BUS (BUS IN) is electrically isolated from
the rest of the card. As a result, the V- input terminal must only be
connected to the BUS running towards the control panel.
Do not connect the V- terminal for the incoming BUS to
other V- terminals present, and do not use it as a reference
for outgoing power supply voltage values.
This could damage the devices used, or cause them to
malfunction.
Earth connection
For standard-compliant installation, connect the earth terminal to the
system earth, passing through the power supply earth connection
using the yellow/green cable supplied with the device housings.
Art. 30003106 technical specifi cations
Output voltage operating range
(VBUS, VAUX1, VAUX2)
V+BUS IN input voltage operating
range
Maximum Open collector output
current: O1-O2-O3
Maximum current for Outputs
V+AUX1, V+AUX2, V+ BUS OUT
Operating temperature
Dimensions - card only (W x H x D)
Weight - card only
Consumption in standby
Batteries supported
Features linked to the type of power supply unit connected to
terminal J1:
Power supply
30076101
unit
Power supply
unit type
TYPE A
(EN50131-6)
100 - 240V ±
Input voltage
10%
AC input
50 ~ 60 Hz
frequency
13.8 Vdc ± 2%
Output voltage
(1.5A Max)
Art. 30076003
Batteries
12V/7Ah
that can be
Art. 30076004
connected
12V and 15Ah
Output voltage
150mV
ripple
To guarantee system certifi cation, the power supply unit must be
positioned in boxes protected by an anti-opening switch, or in
the control panel housing. The 24h input must be connected to a
balanced line, and connected to a VEDO system input line.
ALARM
SINGLE BALANCED
10.3 - 14.5 Vdc
10 - 15 Vdc
100 mA
1.5 A
+5°C to +40°C, Relative Humidity
90%
140 x 127 x 23 mm
90 g
25 mA
Art. 30076003 - 12V and 7Ah
Art. 30076004 - 12V and 15Ah
30076102
30076103
TYPE A
TYPE A
100 - 240V ±
100 - 240V ±
10%
10%
50 ~ 60 Hz
50 ~ 60 Hz
13.8 Vdc ± 2%
13.8 Vdc ± 2%
(3A Max)
(5A Max)
Art. 30076003
Art. 30076003
12V/7Ah
12V/7Ah
Art. 30076004
Art. 30076004
12V and 15Ah
12V and 15Ah
150mV
300mV