Installation Instructions
External Power Supply (24V)
Bloc d'alimentation externe - 24V
Fuente de alimentación externa - 24V
General Information
The External Power Supply is a system accessory for the
Greengate Lighting Control System. It is used to power
user interfaces and other accessories when additional
power is needed.
The EXPS-24V will provide an isolated 24 VDC to
power an additional 24 Greengate Digital Switch station
beyond what the panel can power on its own (see
panel installation instructions). The EXPS-24V requires a
constant 120 VAC power connnection.
Greengate Lighting Control Panels
Model# EXPS-24V
The following instructions should be followed.
1.
Mount the EXPS-24V in a convient location to access
the digital switch network wire (LCCP or LCCNP) as
well as 120 VAC constant power.
2.
Connect the EXPS-24V DC OUT Black wire to the
LCCP or LCCNP Black (OV) wire.
3.
Connect the EXPS-24V DC OUT Red wire to the
LCCP or LCCNP Red (+24V) wire.
4.
Connect the EXPS-24V AC In Blue wire to Neutral.
5.
Connect the EXPS-24V AC In Brown wire to 120 VAC
constant Hot.
GDS-3TLB-W
GDS-1TLB-W
1,000 ft
Maximum
INS #
Additional 25 Devices
EXPS-24V