Daikin 3MXM40N2V1B Manual De Instalación
Ocultar thumbs Ver también para 3MXM40N2V1B:
Tabla de contenido

Publicidad

Enlaces rápidos

Installation manual
R32 Split series
3MXM40N2V1B
3MXM52N2V1B
3AMXM52M3V1B
3MXM68N2V1B
3AMXF52A2V1B
3MXF52A2V1B
3MXF68A2V1B
4MXM68N2V1B
Installation manual
4MXM80N2V1B
English
R32 Split series
5MXM90N2V1B

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Daikin 3MXM40N2V1B

  • Página 1 Installation manual R32 Split series 3MXM40N2V1B 3MXM52N2V1B 3AMXM52M3V1B 3MXM68N2V1B 3AMXF52A2V1B 3MXF52A2V1B 3MXF68A2V1B 4MXM68N2V1B Installation manual 4MXM80N2V1B English R32 Split series 5MXM90N2V1B...
  • Página 2 2P427092-11R...
  • Página 3 2P427092-11R...
  • Página 4 2P427092-19T...
  • Página 5 2P427092-19T...
  • Página 6: Tabla De Contenido

    About heat mode lock ..........14 Daikin website (publicly accessible). 4.6.6 About cool mode lock..........14 ▪ The full set of latest technical data is available on the Daikin 5 Commissioning Business Portal (authentication required). Checklist before commissioning..........15 Checklist during commissioning ..........15 Trial operation and testing............
  • Página 7: About The Box

    2 About the box 3.1.1 Installation site requirements of the About the box outdoor unit Mind the following spacing guidelines: Outdoor unit >100 >350 2.1.1 To remove the accessories from the >100 outdoor unit >50 1× 1× 1× 1× 1× (mm) (mm) Air outlet...
  • Página 8: Refrigerant Piping Length And Height Difference

    4 Installation Prevailing wind direction Mounting the outdoor unit Air outlet It is recommended to provide at least 150  mm of free space below 4.1.1 To provide the installation structure the unit (300 mm for heavy snowfall areas). Additionally, make sure the unit is positioned at least 100 mm above the maximum expected Use a vibration-proof rubber (field supply) in cases where vibrations level of snow.
  • Página 9: To Prevent The Outdoor Unit From Falling Over

    4 Installation NOTICE CAUTION If the drain holes of the outdoor unit are blocked up by a ▪ No brazing or welding on site for units with R32 mounting base or floor surface, place additional foot bases refrigerant charge during shipment. ≤30 mm under the outdoor unit's feet.
  • Página 10: To Connect The Refrigerant Piping To The Outdoor Unit

    4 Installation Coat the threaded connection port of the outdoor unit where the flare Port Class Reducer nut comes in with refrigeration oil. C + D 15, 20, 25, 35 Flare nut for (mm) Tightening torque (N•m) 42, 50, 60 Ø9.5 33~39 —...
  • Página 11: To Perform Vacuum Drying

    4 Installation 1 Charge the system with nitrogen gas up to a gauge pressure of WARNING at least 200  kPa (2  bar). It is recommended to pressurize to ▪ Do NOT pierce or burn refrigerant cycle parts. 3000 kPa (30 bar) in order to detect small leaks. ▪...
  • Página 12: To Fix The Fluorinated Greenhouse Gases Label

    4 Installation 2 Charge the additional refrigerant amount. WARNING 3 Open the gas stop valve. ▪ Do NOT use locally purchased electrical parts inside the product. 4.4.5 To fix the fluorinated greenhouse gases ▪ Do NOT branch the power supply for the drain pump, label etc.
  • Página 13: To Connect The Electrical Wiring On The Outdoor Unit

    4 Installation Model 3MXM40, 3- core cable 2.5 mm 20 A 3AMXM52, H05RN-F (60245 IEC 57) 3AMXF52, H07RN-F (60245 IEC 66) 3MXF52 3- core cable 4.0 mm 3MXM52, 25 A 3MXF68, 1 2 3 H07RN-F (60245 IEC 66) 3MXM68, 4MXM68 4MXM80, 3- core cable 4.0 mm 32 A 5MXM90 H07RN-F (60245 IEC 66)
  • Página 14: About Priority Room Function

    4 Installation 1× 3 Turn on the main power supply. 4.6.3 About priority room function INFORMATION 2 Set the night quiet mode switch (SW6-1) to ON. ▪ The priority room function requires initial settings to be made during the installation of the unit. Ask the 4.6.5 About heat mode lock customer in which rooms he plans to use this function...
  • Página 15: Commissioning

    Next commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Trial operation and testing Business Portal (authentication required). For the Hybrid for Multi, certain precautions are required before The general commissioning checklist is complementary to using this function.
  • Página 16: To Perform A Test Run

    6 Disposal INFORMATION ▪ Test run can be disabled if necessary. 1× ▪ After the unit is turned OFF, it cannot be started again for 3 minutes. ▪ When the test run is started in the heat mode right after turning the safety breaker on, in some cases no air will be output for about 15 minutes in order to protect the unit.
  • Página 17: To Start And Stop Forced Cooling

    Liquid stop valve Daikin website (publicly accessible). To start and stop forced cooling ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 1 Turn OFF the power. 2 Remove the service cover and the switch box cover.
  • Página 18: Piping Diagram: Outdoor Unit

    7 Technical data Symbol Meaning Symbol Meaning BZ, H*C Buzzer Limit switch Capacitor Float switch AC*, CN*, E*, HA*, HE*, HL*, Connection, connector S*NPH Pressure sensor (high) HN*, HR*, MR*_A, MR*_B, S*, U, S*NPL Pressure sensor (low) V, W, X*A, K*R_* S*PH, HPS* Pressure switch (high) D*, V*D...
  • Página 19 7 Technical data 3MXM40, 3MXM52, 3AMXM52, 3AMXF52, 3MXF52 7.9CuT 7.9CuT 6.4CuT (6.4CuT) 7.9CuT 7.9CuT 12.7CuT 7.9CuT 7.9CuT 6.4CuT 9.5CuT (6.4CuT) 7.9CuT 9.5CuT 7.9CuT 6.4CuT 9.5CuT (6.4CuT) 12.7CuT 9.5CuT 12.7CuT 15.9CuT 12.7CuT (9.5CuT) 9.5CuT 12.7CuT (12.7CuT) 12.7CuT (12.7CuT) 15.9CuT 12.7CuT 3MXM68, 3MXF68 7.9CuT 7.9CuT 6.4CuT...
  • Página 20 7 Technical data 4MXM68 7.9CuT 7.9CuT 6.4CuT (6.4CuT) 7.9CuT 7.9CuT 12.7CuT 7.9CuT 7.9CuT 6.4CuT 9.5CuT (6.4CuT) 7.9CuT 9.5CuT 7.9CuT 6.4CuT (6.4CuT) 7.9CuT 6.4CuT 6.4CuT 9.5CuT (6.4CuT) 9.5CuT 9.5CuT 12.7CuT 12.7CuT 15.9CuT 12.7CuT 15.9CuT 9.5CuT 12.7CuT (9.5CuT) 9.5CuT 12.7CuT (9.5CuT) 12.7CuT (12.7CuT) 15.9CuT 12.7CuT...
  • Página 21 7 Technical data 5MXM90 7.9CuT 7.9CuT 7.9CuT 6.4CuT 9.5CuT (6.4CuT) 7.9CuT 9.5CuT 7.9CuT 6.4CuT 7.9CuT (6.4CuT) 7.9CuT 12.7CuT 7.9CuT 7.9CuT 7.9CuT 6.4CuT 9.5CuT 7.9CuT (6.4CuT) 9.5CuT 7.9CuT 7.9CuT 7.9CuT 6.4CuT 6.4CuT 9.5CuT (6.4CuT) 9.5CuT 7.9CuT 6.4CuT (6.4CuT) 9.5CuT 12.7CuT 12.7CuT 15.9CuT 12.7CuT 15.9CuT...
  • Página 24 3P600450-1 2019.10...

Tabla de contenido