5.2.3 Appendix: Reference of normal operation parameters
No
Debug item
1
2
3
4
ODU
parameters
5
6
7
8
9
10
11
12
13
parameters
14
Communication
15
parameters
16
Drainage system
17
Others
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Parameter name
Outdoor temperature
Compressor
discharge temp
Defrosting temp
System high pressure
System low pressure
Opening angle of
thermal EXV
Compressor's
operating freq
Compressor's
operating current
Compressor's IPM
temp
Fan motor's operating
freq
IDU ambient temp
Indoor heat
exchanger's inlet
temp
Indoor heat
IDU
exchanger's inlet
temp
Opening angle of
indoor EXV
Communication data
——
——
DC Inverter Multi VRF System User Manual
Unit
Reference
●When compressor starts, discharge temp in cool
mode is within 70~105℃ and at least 10℃ higher
than the high pressure saturation temp;
●As for temp in heat mode, it is within 65~90℃
and at least 10℃ higher than the high pressure
saturation temp.
●In cool mode, defrosting temp is 4~10℃ lower
than system's high pressure value;
●In heat mode, defrosting temp is about 2 ℃
different from system's low pressure value.
●In cool mode, the normal high pressure value is
within 20 ℃~55℃. According to the change of
ambient temp and system's operating capacity, the
high pressure value will be 10℃~30℃ higher than
ambient temp. The higher ambient temp is, the
smaller temp difference is. If ambient temp is
25~35℃ in cool mode, system's high pressure
value will be within 44~53℃.
●In heat mode, if ambient temp is above -5℃,
system's high pressure value is within 40~52℃. If
ambient temp is low and many IDUs are turned on,
the high pressure will be lower.
●When ambient temp in cool mode is 25~35℃, the
low pressure value is 0~8℃.
●When ambient temp in heat mode is above -5℃,
the low pressure value is -15~8℃.
●In cool mode, the thermal electronic expansion
PL
valve remains 480PLS.
S
●In heat mode, the adjustable opening angle of
EXV is 40~480PLS.
HZ
Changes in 10Hz~80Hz.
When compressor works normally, the current is
A
no more than 18.4A.
When ambient temp is below 35℃, IPM temp is
lower than 80℃ and the highest temp won't be
above 95℃.
Changes in 0~49Hz according to system's
HZ
pressure.
——
●According to ambient temp, for a same IDU in
cool mode, the inlet temp will be 1℃~7℃ lower
than the outlet temp, and 4~9℃ higher than the
low pressure value.
●For a same IDU in heat mode, the inlet temp will
be 10℃~20℃ lower than the outlet temp.
●In cool mode, the opening angle of indoor EXV
PL
varies within 70~480PLS.
S
●In heat mode, the opening angle of indoor EXV
varies within 70~480PLS.
Number of IDUs detected by software is the same
with the actual number. No communication error.
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward
slope of water; Water of outdoor unit can be
drained completely through drainage pipe. No
water drop from unit base.
Compressor and indoor/outdoor fan motor do not
have strange noise. Unit can operate normally.
32
——