Funciones De Modbus - Stübbe UFM MD Flex Serie Instrucciones De Servicio

Tabla de contenido

Publicidad

Anexo

10.4.4 Funciones de Modbus

Func-
Name
tion
Code
01
Read Coil
Status
02
Read Input
Status
03
Read Holding
Registers
04
Read Input
Registers
05
Force Single
Coil
Tab. 20

Funciones de Modbus

1) La denominación de relés (Coils), entradas (Input) y registros comienza con "1" (dirección física "0").
24
UFM
1)
Address
0x00 → RELAY1
0x01 → RELAY2
0x00 → INPUT1
0x01 → INPUT2
0x00 → UFM Version
0x01 → Distance [mm]
0x02 →
0x08 → Error
0x09 → Device ID [UFM]
0x0A → Distance [mm]
0x0C → Filling Level [cm]
0x0E → Volume [l]
0x14 → Temperature [°C]
-
0x00 → RELAY1
0x01 → RELAY2
Data type
Comment
Bit
Read relay status.
Bit
Read input status.
A "TRUE" logic level on the inputs are
extended to minimum 5 seconds.
Unsigned
Value = 310 → V3.10
Integer
Signed Integer
Value = 0 ... 10.000 → 0 ... 10 Bar
-
Signed Integer
Unsigned
TRUE → Sensor error
Integer
FALSE → Sensor OK
Unsigned
Value = 50 → Device ID = 50
Integer
Float_ABCD
IEEE 32-bit floating-point
Float_ABCD
IEEE 32-bit floating-point
Float_ABCD
IEEE 32-bit floating-point
Float_ABCD
IEEE 32-bit floating-point
-
-
Bit
Write relay status, if it is released to Mod-
bus control
value = 0x0000 → Relay off
value = 0xFF00 → Relay on
BA-2016.11.18 ES