This document contains installation instructions
for the Eve Double Pro-line. Please always refer
to our website for the most up-to-date and
complete manual for the product.
www.alfen.com/en/downloads

Installation conditions

The installation must comply with standards
and (local) regulations and must only be carried
out by a qualified technician.
Conditions of use
Operating temperature
Relative humidity
Electrical safety class
Protection rating
Mechanical impact
Nominal input voltage
Single-phase
230 V ± 10%
3-phase
400 V ± 10%
Earthing
TN or IT
PE cable
system
self-installed earth electrode,<100
TT system
Ohm earth dispersion resistance
If there are two power supply cables, the
following safety devices are required on each
power supply cable.
Short-circuit protection (system circuit breaker)
Single-phase
2x 20 A, 1Ph,
16 A
char. B or C
2x 40 A, 1Ph,
32 A
char. B or C
Short-circuit protection (cartridge fuses)
Single-phase
16 A
2x 20 A gG
32 A
2x 35 A gG
Residual current device (optional)
Single-phase / 3-phase
16 A
Type B (selective), 100 mA, 20A
32 A
Type B (selective), 100 mA, 40A
Minimum power supply cable diameters
(max.50m)
Single-phase
2
16 A
4 mm
2
32 A
6 mm
-25 °C / +40 °C
5% / 95%
I
IP54
IK10
50 Hz
50 Hz
3-phase
2x 20 A, 3Ph,
char. B or C
2x 40 A, 3Ph,
char. B or C
3-phase
6x 20 A gG
6x 35 A gG
3-phase
2
4 mm
2
6 mm
6
8
10
4
2
3
single
dual
power supply
power supply
output
input
output
input
PE
PE
N
L1
L1
L2
L2
L3
L1
L3
L2
N
L3
N
1
11
4
5
6
7
9
8
10
}
L
}
R