Page 18
ENGLISH
4.4
Fill Time before Lockout
Model K-1100 and LX2:
For the K-1100 and LX2 the factory-set Fill time before
Safety Lockout occurs is 20 minutes. The Fill time can
be modified by cutting the jumpers as follows:
Cut Jumper
Fill Time Period
Either A or B
40 minute fill before lockout
Both A and B
60 minute fill before lockout
NOTE To disable the lockout feature, cut jumper S-1.
See Figure 26 for the location of the LX2 jumpers and
Figure 27 for the location of the K-1100 jumpers.
Model LEV110CK/2G:
The LEV110CK/2G factory-set Fill time before Lockout
is one (1) hour. To modify, cut jumpers as follows:
Cut Jumper
Fill Time Period
Either A or B
2 hours fill before lockout
Both A and B
3 hours fill before lockout
NOTE To disable the lockout feature, cut jumper S-1.
See Figure 27 for location of LEV110CK/2G jumpers.
Model K-2300: The K-2300 factory-set Fill time before
Lockout is 20 minutes for both Filling I and Filling II.
To modify fill times, cut jumpers as follows:
Cut Jumper
Fill Time Period
Either A or B
40 minute fill before Filling I lockout
Both A and B
60 minute fill before Filling I lockout
Either C or D
40 minute fill before Filling II lockout
Both C and D
60 minute fill before Filling II lockout
NOTE To disable Filling I lockout, cut jumper S-1. To
disable Filling II lockout, cut jumper S-2.
See Figure 28 for the location of the K-2300 jumpers.
Jumper
S 1
Cables
A
B
Figure 26. LX2 Jumper Cables
Jandy Levolor
Models K-1100, LX2, K-2300, and LEV110CK/2G
PCB
Transformer Enclosure
Electronic Water Leveler
®
Jumper
Cables
Figure 27. K-1100 and LEV110CK/2G Jumper Cables
Jumper
Cables
Figure 28. K-2300 Jumper Cables
|
Installation and Operation Manual
S 1
A
B
S 1
A
B
S 2
C
D