LEGRAND 625 30 Manual Del Usuario página 6

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 17
Connection
N
230 V
50/60 Hz
L
Powering up
• Flashing green LED (batteries charging)
• LED standby indicator comes on
Operation
Mains supply present
• Unit on standby
• LED standby indicator comes on
Automatic unit status check (SATI system)
The unit automatically tests its operating state
- once a week : switching to emergency mode and lamp test for 15 seconds.
- once every quarter (13 weeks) : switching to emergency mode for 1 hour and battery life test.
Results of automatic checks
Indicator
green
yellow
A+
Remote control box Cat. No. 039 00/01, or addressable central unit
Cat. No. 625 15 / Repeater Cat. No. 625 12
B–
After 12 hours charging
Unit OK
Battery fault
(steady or flashing)
(slow flashing)
If the power supply and remote control are reversed,
!
the unit will be terminally damaged
Important :
before doing any work on the cabling of the addressable units
de-energise the installation and put the units to rest
• Green LED on, unit OK
Mains supply absent
• Unit in operation (emergency)
• Emergency lamps come on
• LED standby indicator goes off
Lamp fault
(steady)
6
Electronic fault
(fast flashing)

Publicidad

Tabla de contenido
loading

Tabla de contenido