Description
This document includes installation information for the
IU2080C indicating circuit controller. The IU2080C provides a
supervised output for sounders and strobes when used with
compatible addressable control panels.
The module is powered by an auxiliary 24 V power supply and
can provide an output power of up to 3 A. The external power
supply is monitored for a low voltage and the external fault
relay for open circuit.
With the required end-of-line resistor installed, the module
monitors the indicating circuit for short circuit and open circuit.
Installation
Caution:
This product must be installed by qualified personnel
adhering to the EN 54-14 standard and any other applicable
local authority laws.
Module layout
Figure 2 shows:
1.
Power LED (green)
2.
Indicating circuit alarm LED (red)
3.
TB1 COM1 input
4.
TB1 COM2 input
5.
TB2 Fault relay (negative)
6.
TB2 Fault relay (positive)
7.
TB3 Audio output 1 (AC1)
8.
TB3 Audio output 2 (AC2)
9.
TB4 Sounder output
10. TB4 Internal end-of-line resistor connector
11. TB4 Auxiliary 24 V power supply connector
12. TB4 AC configuration jumpers JP1 and JP2
Note:
Terminal block labelling TB1, TB2, TB3, and TB4 is for
reference purposes only and does not refer to printed texts on
the module PCB.
Assembly
Install the module into the protective housing as shown in
Figure 1. Connecting cables should be fed through cable entry
hole at the rear of the protective housing before the module is
fixed into place.
Y/Z style wiring
The module can be wired for connection styles Y and Z. Wiring
requirements – indicated in Figures 3 to 6 - will vary depending
the use of a power supply fault relay.
Figures 3 to 6 show:
1.
24 VDC auxiliary power supply
2.
Sounder output
3.
Fault
4.
Loop input
5.
Loop output
6.
Fault relay contacts
P/N 55370163 • REV 04 • ISS 30OCT13
Key to Y/Z wiring options shown in Figures 3 to 6:
Figure
Style
Power supply fault relay
3
Y
No
4
Z
No
5
Y
Yes
6
Z
Yes
AC operation wiring
Caution:
Remove jumpers JP1 and JP2 for AC operation.
Figure 7 shows:
1.
24 VDC auxiliary power supply (from control panel)
2.
Sounder output
3.
Fault
4.
Loop input
5.
Loop output
6.
To audio transformer, secondary side (AC signal 70 Vrms)
7.
To audio trunk supervisory voltage (rectified AC>2.5 V)
Fault signal indication with open collector driver
Figure 8 shows fault signal indication with an open collector
driver.
Addressing
Each module must be assigned an address from 1 to 128. Use
the rotary dial marked 0 to 12 to set the tens and hundreds part
of the address, and the rotary dial marked 0 to 9 for the
remaining digits. See Figure 9 for sample address settings.
Note:
To overcome the mechanical effects of shipping and
storage we recommend that you first rotate each dial counter-
clockwise (to the 0 position) and then clockwise (to the dial's
maximum position) before setting the required address.
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Loop input
Operating voltage
Current consumption in standby
Current consumption in alarm
External power supply
Low voltage detection
Fuse rating
Sounder circuit
Circuit impedance at 24 V:
Short circuit
Standby
Open circuit
Supervisory voltage
End-of-line resistor
Current consumption in standby
17 to 28 VDC
< 350 µA (< 200 µA typical)
< 3.5 mA
24 V: < 20.4 V
3 A
< 3.3 K
< 3.3 to 13 K
> 13 K
2.2 VDC, inverted
10KΩ, 5%, 1/4W
< 11 mA @ 24 VDC