PANEL COMPATIBILITY
MAXIMUM VOLTAGE ACCEPTED BY THE REGULATOR
There are 2 panel voltages:
The operating voltage (Vmp)
•
Standby voltage (Voc)
•
To choose an MPPT, it is necessary to refer to he Voc voltage of the panel which corresponds to the
open circuit voltage.
In series the Voc add up chile in parallel not.
Example panels 100W – 12V monocrystalline (= 100W / 21.3 Voc)
In serie:
In parallel:
Uniteck recommends a parallel connection for better electrical efficiency and to avoid losses due to shading
!
MAXIMUM PANEL POWER ACCEPTED BY THE CONTROLLER
UNIMPPT 60/30.24S (60 Voc panel – bat charge 30A -12V/24V)
1 panel*
2 panels*
3 panels*
4 panels*
*Total Voc: 60V (see section Maximum voltage accpeted by the regulator)
26/52
+
+
= 300W and 63.9 Voc
+
+
= 300W and 21.3 Voc
UNIMPPT
60/30.24S
UNIMPPT
60/40.24S
UNIMPPT
100/60.24S
*Be careful, a voltage higher than the maximum voltage (Voc) can
damage the charge regulator. Damage not covered by the warranty.
With 12V battery
Max pan. : 450W
Max pan. : 200W (x2)
Max pan. : 150W (x3)
Max pan. : 110W (x4)
Panel voltage (Voc)
Max
60V*
60V*
100V*
www.uniteck.fr
Adated regulator
UNIMPPT 100/60.24S
UNIMPPT 60/30.24S
Min
17V (Batt 12V)
34V (Batt 24V)
17V (Batt 12V)
34V (Batt 24V)
17V (Batt 12V)
34V (Batt 24V)
With 24V battery
Max pan. : 900W
Max pan. : 200W (x2)
Max pan. : 200W (x3)
Max pan. : 150W (x4)