IFMEXT LED
CAN
EXT
HOLD
PRE-EXT
REL
Terminal
The pressure-switch input is for the
connection of a pressure switch
PRESSOS.
which will close the contact in the
event of low pressure in the cylinders.
This input stops the extinguishment
STOP-EXT
procedure in accordance with the
activation mode described opposite.
This input is for the connection of
one or more manual call points for
MAN.-EXT
the activation of extinguishing-agent
Output for the connection of the
VALVE
electrovalve which discharges the
extinguishing agent.
Output for the connection of lock-
HOLD
extinguishment signalling devices.
Output for the connection of a signal
PRE-EXT
relating to imminent discharge of the
extinguishing agent.
Output for the connection of
signalling devices which warn
RELEASED
building inhabitants of the actual
discharge of the extinguishing agent.
Note:
The functions shown in the table, with the exception of the "VALVE" output, can be
replicated on the input/output devices of the loop or IFM internal modules.
8
Colour
Blue
Red
Yellow
Red
Yellow
Red
Yellow
Red
Yellow
Function
discharge.
Activity on the CAN communication BUS
Extinguishment activated (running or ended)
Fault on VALVE terminal line
Extinguishment locked manually or automatically
Fault on the line of the HOLD terminal
Pre-extinguish phase running
Fault on the line of the PRE-EXT terminal
Extinguishment terminated
Fault on the RELEASED terminal line
If the electrovalve opens when the "verify" procedure is enabled, its
activation confirms the discharge of extinguishant gas (refer to the
"confirm" option below).
During stand-by status, its activation generates a fault warning.
If this input is activated during the pre-extinguishment phase,
the extinguishment procedure will be aborted even if the input
Abort
The procedure can be restarted only after control panel reset.
If activated during stand-by, it will generate a fault warning.
If this input activated during pre-extinguishment status, the
extinguishment procedure will remain locked until the input
resets. On input reset the pre-extinguishment countdown will
Add
If this input is activated during stand-by, it will generate a fault
If this input is activated during pre-extinguishment status, the
extinguishment procedure will remain locked but the pre-
extinguishment countdown will continue running. On input
Hold
reset, if the early warning countdown has terminated, the
extinguishant gas will be discharged.
If this input is activated during stand-by, it will generate a fault
This function is identical to the "Hold" function but refers to
mechanical or electrical intervention (for example, a door
External
contact that inhibits gas discharge, etc.).
This activation will be signalled separately.
If activated during stand-by, it will not generate a fault warning.
It will activate only when the pre-extinguishment time expires
It will activate when the extinguishing channel is locked by one or more
inputs connected to a "STOP-EXT" input.
It will activate during the pre-extinguishment time which runs before the
discharge of the extinguishing agent.
It will activate on activation of the electrovalve.
On solid
Activation
resets.
refresh and restart.
warning.
warning.