ELECTRONIC VOLTAGE ABSENCE
DETECTOR
ENGLISH
SELF-CHECKING TEST
Before and after use of the voltage detector you must perform a
self-checking test for correct operation.
The voltage absence detector uses an integrated electronic device to perform
the self-checking of the correct operation indicator and power circuits.
The self-checking test is activated by pushing the test button at least during
2 seconds (4). If this time is not respected the self-checking test will indicate
an error by producing a disturbing sound and powering off.
When pressed correctly and the detector is suitable for use, it is stated by
an intermittent buzzer (7), all at once with the optical signal by red LED (5),
green (6) and orange (8).
When the test button is no longer pressed, if the test result is correct, the
device remains in alert status with the green LED on (6). If the result of the
test is not correct, it will produce a disturbing sound and it will powers off.
The alert status continues for a period of 2 minutes before automatic
disconnection.
If the device detects that the battery voltage level drops below the safe
threshold it stays inoperative and it turns off.
In this case proceed to change the battery (see battery change).
VOLTAGE ABSENCE TESTING
1.- Fit the voltage detector at the end of an appropriate insulated pole to the
voltage range and with universal head (3).
2.- Push the on/test button (4) to put the detector in alert mode, green LED on.
3.- Put the electrode (1) of the detector in contact with the conductor to operate it.
Results of the test:
- VOLTAGE PRESENCE, red LED and buzzer activated (5 and 7).
- VOLTAGE ABSENCE, detector remains in alert mode, green LED (6).
In case of the "voltage absence" result, it is necessary to perform the test again.
In addition to the self-checking test, it is a good idea to check the indication
of "voltage presence" on a service voltage supply before each use.
MAINTENANCE
Keep the voltage detector clean.
Transport and store the device in the supplied briefcase.
Prevent any blow. In case of fall, break or detection of any anomaly,
contact SOFAMEL, S.L. for its inspection, repair or calibration.
Even if it is stored, the voltage detector should be checked and
calibrated by the manufacturer after a maximum of 6 years.
BATTERY REPLACEMENT (Fig. 1)
For battery replacement a screwdriver is required.
1.- Unscrew the contact electrode (1).
2.- Separate the housing and plastic piece.
3.- Change battery.
FEATURES
Voltage Range:
It fulfil electrically UNE-EN 61243-1:2006+A1:2011
(except range)
Voltage Threshold (Vt) between phase and earth:
VtMIN
VTE-5/36-U
1.800 V
VTE-5/66-U
1.800 V
Voltage range (Vr) among phases:
VrMIN
VTE-5/36-U
5.000 V
VTE-5/66-U
5.000 V
Frequency:
50 Hz - 60 Hz
Type:
Capacitive
Use:
Indoor/Outdoor use, through appropriate insulated
pole according to the voltage detector range.
Signal:
Visual and audible through LEDS and buzzer.
Indicators group:
3, detector with alert state and indicator of "Voltage
presence".
Climate category:
N, climate conditions for use and storage, temperature
from -25°C to +55°C, humidity from 20% to 96%.
Class:
L, detector without contact electrode extension.
Power supply:
6LR61 battery, automatic disconnect system at low
voltage threshold.
Self-checking:
Integrated device for operational self-checking.
Auto-start:
The detector includes an auto start system in case of
detection of "voltage presence" when it is in the off
mode.
VtMAX
< V t <
2.400 V
< V t <
2.400 V
VrMAX
to
36.000 V
to
66.000 V