2.6 Technical data
2.6.1
Refrigeration data
Designation
Cooling capacity (L 35 / W 10 /
400l/h) *
Coolant
Thermostat setting
Thermostat setting range
Water quantity *
Water supply temperature
Operating pressure *
Air volume flow
Ambient air temperature
Switch cabinet interior temperature
Duty cycle
Sound pressure level (1m)
Condensate separation
2.6.2
Electrical data
Designation
Rated
operating
voltage * / **
Rated frequency *
Power consumption *
Rated current*
Max. rated current
UL at 60 Hz *
Starting current +
Upstream fuse T *
Functional range
Temperature monitoring (Alarm)
Switching point via setpoint
2.6.3
Dimensions
Designation
Height x width x depth PWS
Height x width x depth PWI
Weight
Installation position
Unit construction
2.6.4
Other unit data
Designation
Cooling water connection
Anti-corrosion protection
Protection type
*
Data on the type plate.
Operating manual PWS and PWI 6302 086100049a © Pfannenberg GmbH
Model PWI/PWS 6302/ 400V
Model PWI/PWS 6302/ 400V
50 Hz
P
el
53W
A35/W10
0,4 A
I
nom max
I
nom max
60Hz UL
I
0,49 A
Start max
Model PWI/PWS 6302/ 400V
Model PWI/PWS 6302/ 400V
Hose nozzle in accordance with DIN 8542 R1/2'' (13 mm)
Standard: Galvanized, electrostatic powder-coated (200°C) Variant:
Stainless steel cover
When used as intended:
IP 55 against the switch cabinet (EN 60529).
**With a change to the rated operating voltage, adapt the upstream fuse;
see
3000 W
Water
+35°C / 95°F
min. 8°C / 46,4°F - max. 50°C / 122°F
400 l / h
10°C (>+1°C bis +35°C)
1 to 10 bar
885m
+1°C / 34°F . . . +70°C / 158°F
+1°C / 34°F . . . +50°C / 122°F
100%
≤ 54 db (A)
Condensate drain (pipe
400V
60 Hz
75 W
0,4 A
0,4 A
0,59 A
2 A gG
DIN IEC 60038
Max. 230V AC, 8 (1,5) A cosφ=1 (0,6)
Max. 230V DC, 0,25 A
+10K
1556 x 485 x 142 mm
1549 x 485 x 142 mm
PWI: 29,5 kg / PWS: 28kg
Vertical
Standard: Steel sheet
Adapting the upstream fuse
Model PWI/PWS 6302/ 460V
3
/ h
ᴓ
=12mm)
Model PWI/PWS 6302/ 460V
460 V
60 Hz
72 W
0,4 A
0,4 A
0,59 A
Model PWI/PWS 6302/ 460V
Model PWI/PWS 6302/ 460V
.
Page 8 / 31