Triggered input 1
<TEXT1>:
Pump failure
Triggered input 2
<TEXT2>:
Water level too low
Power failure
<TEXT3>:
Mains power failure
Power restoration
<TEXT4>:
Mains power restored
<CODE> TEXT1:<free text>
SMS commands text 1:
<CODE> TEXT2:<free text>
SMS commands text 2:
.... similar for TEXT3 and TEXT4
3.4.4 Power failure delay time
The power failure delay time defines the time that the power fails before an alarm is initiated. If the power is restored within the delay time, no alarm is sent. The time can be
set between 0 and 999 minutes. As default, the delay time is set to 0.
<CODE> DELAYPOW:xxx
SMS command power failure delay time:
3.4.5 Input type
The input type defines the character of the inputs IN1 and IN2. This can be Normally Open (NO) or Normally Closed (NC). In case an input is set to NO, the alarm will be trig-
gered as soon as the terminals of the input are closed. If the input is set to NC, the alarm is triggered in case the connection between the input terminals is broken. The default
input type is set to NC.
<CODE> TYPEIN1:xx
SMS command input type input 1:
<CODE> TYPEIN2:xx
SMS command input type input 2:
3.4.6 Input delay time
The input delay time defines the time that the input are triggered before an alarm is initiated. If the input returns to the non-alarm status within the delay time, no alarm is
sent. The time can be set between 0 and 999 seconds.
As default, the input 1 delay time is set to 60 second, the input 2 delay time to 1 second.
<CODE> DELAY1:xxx
SMS command alarm delay input 1:
<CODE> DELAY2:xxx
SMS command alarm delay input 2:
3.4.7 Inactive time
The "inactive time" defines the time input 1 or input 2 is not active after an activation. In case the time is set to "0" (minutes), the input is active again immediately after
returning to the non-alarm status. In case the time is set to e.g. 30 minutes, the input remains inactive for the first 30 minutes. In case the input is again (or still) activated
after these 30 minutes, a new alarm message is sent.
The time can be set between 0 and 60 minutes. As default, the inactive time is set to " 0".
<CODE> INACTIVEIN1:xx
SMS command inactive time input 1:
<CODE> INACTIVEIN2:xx
SMS command inactive time input 2:
3.4.8 Alarm repeat time
In order to emphasize the urgency of the alarm messages, all alarms can be repeated. As long as the alarm status has not returned to the inactive status, the SMS alarm will
be repeated after the ' alarm repeat time' . The time can be set between 0 and 24 hours. As default the alarm repeat time is set off (0).
<CODE> REPEAT:xx
SMS command alarm repeat time:
3.4.9 Test SMS text message
The SMS-Alert can send regular test SMS messages (´keep alive') to the administrator, to ensure the proper functioning of the unit. The test message function is only active
in case the unit is armed.
The interval between the test messages can be set between 0 days (no test message) and 30 days. The default test interval is set to 0 (no test message).
<CODE> TEST:xx
SMS command interval test message:
8
3.5 LIST OF SMS COMMANDS FOR CONFIGURATION
Setting
SMS Command
Change security code
INSTCODE:<xxxx>
Set telephone number for alarm messages
TEL1:<tel number>
....
TEL5:<tel number>
Delete telephone number
DEL1
....
DEL5
Identification text
NAME: <text>
Power failure delay time
DELAYPOW:<min>
Input type (input 1)
TYPEIN1:<type>
Input type (input 2)
TYPEIN2:<type>
Delay on input 1
DELAY1:<sec>
Delay on input 2
DELAY2:<sec>
Inactive time input 1
INACTIVEIN1:<min>
Inactive time input 2
INACTIVEIN2:<min>
Alarm repeat time
REPEAT:hh
Alarm text input 1
TEXT1:<text>
Alarm text input 2
TEXT2:<text>
Alarm text after power failure
TEXT3:<text>
Alarm text after power restoration
TEXT4:<text>
Interval ' test SMS'
TEST:<days>
Examples:
Set phone number1 :
1111 TEL1:0612345678
Delete phone number1:
1111 DEL1
3.6 RESET OF SYSTEM
To reset the SMS-Alert to its factory settings:
• Remove the batteries and external power supply
• Press the outside button while entering the batteries. Keep it pressed for (about) another 5 seconds
• Release the button immediately after the LED starts to flash
• Reconnect the external power supply
After a successful reset, the status LED on the keypad will blink green to indicate that the module is not configured. The security code <CODE> is back to factory settings as
well.
4. REQUEST OVERVIEW OF THE SETTINGS AND STATUS
The programmed settings and status of the GSM detector can be received per SMS message. Before sending the request, make sure the unit is in the program mode (please
refer to 4.1).
4.1 STATUS REQUEST
The status of the SMS-Alert can be requested by sending an SMS with the content:
<CODE> STATUS?
Upon sending this request, the SMS-Alert returns the status to the originator of the request:
• The status message includes the ARMED / NOT CONFIGURED status
• The status of the inputs and the status of the power and batteries
4.2 OVERVIEW GENERAL SETTINGS
The general settings of the SMS-Alert can be requested by sending an SMS with the content :
<CODE> SET?
Upon sending this request, the SMS-Alert returns the list of programmed settings to the originator of the request.
Range
Default value
0000..9999
1111
Empty
20 characters
SMS alert
0..999 (min)
0
NO, NC
NC
NO, NC
NC
0..999 (sec)
60
0..999 (sec)
1
0..60 (min)
0
0..60 (min)
0
0..24 (hrs)
0
20 characters
Pump failure
20 characters
Water level too low
20 characters
Mains power failure
20 characters
Mains power restored
0..30 (days)
0
9