Installation
Installation
Step 1: Mount the bracket to the wall
1. Rough in ½" NPT supply piping (by installer)
from the wall where the eye/face body wash
is desired.
2. Using the bracket flange as a template, mark
the anchor/screw locations on the wall.
3. Mount the bracket to the wall with three
suitable anchors and #8 screws (supplied by
installer).
Step 2: Connect the hose assembly
NOTE: Apply pipe sealant (supplied by installer) to
all male threaded pipe joints.
1. Connect the ½" NPT elbow (provided) to the
½" NPT supply from the wall.
2. Connect the end of the drench hose to the
½" NPT elbow.
3. Mount the safety sign using hardware
supplied by the installer.
4. Open the water supply line. Test for leaks
and adequate water flow.
Assembly of Components and Parts List
3
7
10
R
P.O. Box 309, Menomonee Falls, WI 53051
TEST THIS UNIT EACH WEEK
DIESES GERÄT 1ST WÖCHENTLICH ZU PRÜFEN.
ESSAI HEBDOMADAIRE
Test-operate valve(s) each week and sign below.
Report any malfunctions immediately.
Ventil(e) wöchentlich im Testbetrieb prüfen, bestätigt
durch Unterschrift. Jegliche Störung sofort melden.
Test le fonctionnement des valves chaque semaine et
signe en bas. S'il y à quelque chose qui ne va pas fait
un rapport immédiatement.
Date
Signed
Date
Signed
Datum
Unterschrift
Date
Signed
Date
Signe
Date
Signed
Bradley Corporation • 215-314 Rev. K; ECM 09-05-0028
4
2
1
1.1
9
6
5
8
8"
(203mm)
12"
(305mm)
Item Part No.
Qty. Description
1
S27-265
1
1.1
269-661
1
2
113-544A
1
3
S05-158
1
4
S53-063
1
5
269-053
1
269-054
1
6
169-078
1
7
S70-084
1
8
169-208
1
9
113-006EF
1
10
204-421
1
3/11/10
S19-600, S19-610
Width (from front) 8" (203mm)
Valve Assembly with Handle
Handle only
¼" Close Nipple
Body Wash Sprayhead
Tethered Dust Cover
Hose, 12' (for S19-600)
Hose, 25' (for S19-610)
Reducing Coupling ½" NPT x
3
Wall Bracket
½" NPT Elbow
3
⁄
" Close Nipple
8
Emergency Inspection Tag
⁄
" NPT
8
3