If DI8 should be used as a normal digital input, insert a resistor as indicated below: fig. 5.

4. PHYSICAL CONNECTION OF THE RS-485 INTERFACE

1) Line termination: include line termination (120 ) only at the network ends.
2) Recommended cable: balanced shielding to operate with differential signals (ex.: AFS
series from KMP , etc.);
3) Grounding of the cable shield: connect the shielding to the equipment frame.
Master of the net
(PC, CLP)
Figure 6: CFW-09 network
connection trough RS-485
serial interface

5. TECHNICAL SPECIFICATIONS

The technical specifications of all factories default functions provided by EBE board is
shown at table 2.
Table 2: Factory default Function description and technical specifications of EBE board and
the respective position (XC2 and XC5 conectors).
Connector
Pin
1
XC5
2
1
2
XC2
3
GROUND
4
CFW-09
(EBE Board)
RS-485
Shield of
the cable
Signal
Digital Input for special motor thermistor function, programmable on P270;
Dl8
Connection according to the figures 4 or 5.
DGND
DGND internally grounded by a 249
A-LINE
Isolated RS-485 serial port - A - LINE.
Isolated RS-485 serial port - B - LINE.
B-LINE
SREF
Reference to RS-485.
Ground (Inverter cabinet).
1
Figure 5: Configuration of DI8 to be used as a digital
input (program every function at P270 excepting 16)
CFW-09
(EBE Board)
XC2
Shield of
the cable
Description/Specification
resistor.
CFW-09
(EBE Board)
XC2
3