CYBER SECURITY NOTICE
SV2 Series products contain electronics and software. Care should be taken by the installer / facility management to guard
against unauthorized access to the valve and to the programming interface for parameter modification (if applicable).
Unauthorized access to change the valve wiring interface, replace parts, change device hardware or software should not
be permitted. Failure to do so may pose a safety risk.
A tamper evident label has been placed inside the valve electrical enclosure to indicate if access has occurred. The label
resides between the valve main electronics assembly and the electrical enclosure which houses it.
NOTE: The valve main electronics assembly is field replaceable and as such, this seal must be broken in order to
replace it.
APPLICATION
The Honeywell SV2 Series valve HMITOOL-000 is a color touchscreen HMI display that provides for configuration, monitoring,
and troubleshooting of the SV2 Series safety shut-off valve platform.
The HMITOOL-000 can be used to monitor from 1 to 8 SV2 Series valves wired to a single port. Wiring connections to the HMI
are through a removable 8-pin wiring connector.
AVAILABLE PARTS
Accessory Parts
Transformer
models:
• AT72D1683/U 120VAC to 24VAC, 40Va, universal mount
• AT72D1691/U 208/240VAC to 24VAC, universal mount
• Other models available. See https://customer.honeywell.com
INSTALLATION
1
Preparation and Mounting
The HMI can be mounted on the door panel of an electrical enclosure.
1. Select the location on the door panel to mount the display; note that the device will extend into the enclosure at least 1 inch
(2.54cm) past the mounting surface.
2. For front panel mount: Provide an opening in the panel door 8 in. wide x 5 ½ in. high (203 mm wide x 140 mm high). Use
cutout template provided in Fig. 11 (page 41).
3. For rear panel mount: Provide an opening in the panel door 7 1/8 in. wide x 4 11/16 in. high (181 mm wide x 118 mm high).
Use cutout template provided in Fig. 12 (page 43).
4. Place the HMI display in the opening and use it as a template to mark the location of the four mounting screw holes. Remove
the device.
5. Using pilot holes as guides, drill ¼ in. (6 mm) holes through the panel door.
6. Place the display in the opening, aligning the mounting holes in the device with the drilled holes in the panel.
7. Secure the display to the panel with the four #6-32 screws, nuts, and standoffs provided in the bag assembly in the shipping box.
Replacement Parts
50063482-001/U
Bag assembly includes:
• 8-pin connector
• CR2032 coin battery
• Mounting hardware
• 3 clamp filters (1 for 24VAC power and 2 for Modbus)
2