Página 1
Installation Air Handler Instructions The manufacturer recommends installing AHRI READ CAREFULLY. listed matched indoor and outdoor system. Installing approved matched indoor and KEEP THESE INSTRUCTIONS outdoor system will provide optimum efficiency and best overall system reliability. 31-5000486 Rev. 4 03-21 GEA...
............... . . 22 Record Keeping Thank you for purchase this product from GE Appliances, a Haier company. This installation manual will help you to get the best _______________________________________ performance.
IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING THE SYSTEM WARNING For your safety, the information in this manual must be followed to minimize the risk of fire, electric shock, or personal injury. • Use this equipment only for its intended purpose as Federal regulations require that a technician must described in this manual.
Página 5
IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING THE SYSTEM CAUTION Regulation of cables and circuit breaker differs from each locality. Be aware of these regulations prior to installtion. It is highly recommended that you do not open or close Do not use existing refrigerant lines.
9. GE Appliances will bear no responsibilities for personal • The manufacturer has the right to revise this manual injury or property damage caused by the following: without notice.
Installation Instructions Unit Dimensions Model Dimension inch(mm) Width Depth Height UUY24ZGDA* 21-1/4(540) 21-1/4(540) 48-1/4(1224) 11-5/8(295) 20(508) UUY36ZGDA* UUY48ZGDA* 24-3/4(630) 21-1/4(540) 57(1448) 11-5/8(295) 20(508) UUY60ZGDA* Installation Clearances 24” clearance is required for filter, coil, or blower removal and service access. The air handler can be installed in a closet with a false bottom to form a return air plenum or be installed with a return air plenum under the air handler.
Main Parts Control Box Assembly Blower Wheel Fan Motor Secondary Drain Pan Evaporator Assembly Primary Drain Pan Model Cooling capacity (ton) Optional electric heater (kW) UUY24ZGDA* 5/8/10 UUY36ZGDA* 5/8/10 UUY48ZGDA* 10/15/20 UUY60ZGDA* 10/15/20 Model Motor @ 230V ~, 60Hz UUY24ZGDA* UUY36ZGDA*...
Installation Instructions CAUTION WARNING • This air handler is designed for indoor installation Prior to installation, turn off all electrical power supplies only. Do not install it outdoors. intended for use with this equipment. • When installing the air handler, take consideration to 1.
EPA certified refrigerant technician in accordance with Model External Diameter (inch) established procedures. Gas pipe Liquid Pipe IMPORTANT: UUY24ZGDA* • Connecting refrigerant lines must be clean, UUY36ZGDA* dehydrated, refrigerant-grade copper lines. Air handler UUY48ZGDA* coils should be installed only with specified line sizes UUY60ZGDA* for approved system combinations.
Installation Instructions Install Condensate Drain Install Condensate Drain (cont.) The air handler is provided with 3/4” NPT condensate 1. Pour several quarts of water into the drain pan, drain connections. enough to fill drain trap and line. A field fabricated secondary drain pan with a drain 2.
Installation Instructions Electrical Requirements Model Power Supply Recommended breaker size (A) UUY24ZGDA* UUY36ZGDA* 208/230V-1Ph-60Hz UUY48ZGDA* UUY60ZGDA* Control wiring” to “Electric wiring Wiring Connections Using 18 Gauge Solid Core Copper Wire 1. High and low voltage wires should be led through different rubber rings of the electric box cover.
Installation Instructions Electrical Connections Heater Kit 1. Refer to the table for the appropriate heater kit. Connect to 5/810kw heater Circuit Breaker 2. Check for any physical damage; do not install a Air Handler Supply Voltage damaged heater kit. Wire Connections 3.
Installation Instructions Thermal Expansion Valve (TXV) Factory Installed Expansion Valves: Sensing bulbs are factory installed and clamped to the suction line. For optimum performance, reattach and insulate the bulb at a 10 or 2 o’clock position outside of the cabinet to the main suction line no more than one foot from the suction line connection after brazing is completed.
Installation Instructions Thermostat Connections NOTE: Y means Compressor control signal for the outdoor unit; B which is energized under the heating mode means 4-way valve control signal; D means defrosting signal; R means 24V AC power supply; C means 24V common; G means indoor unit fan signal for the indoor unit;...
Página 17
Installation Instructions Indoor unit Power CB1CB2 CB2 CB1 HEAT HEAT 2 3 4 5 6 Code Name ② Circuit breaker only Code Name for 10KW heat kit Circuit breaker Circuit breaker only 10KW HEAT KIT 15KW/20KW HEAT KIT for 5/10KW heat kit X1 X2 Tube W6 W7...
Installation Instructions Airflow Adjustments Instructions for Connect Series Default airflow settings for the air handler is Level 4. Air flow can be adjusted by using the control board dip switches different speeds according to the system static pressure. Fan speed settings are listed below: 1.
Installation Instructions Final Check Check Items for Test Run System Test Please explain to the customer how to operate the system No gas leak from linesets? by using the Owner’s Manual found with the indoor unit. Are the linesets insulated properly? Are the connecting wirings of indoor and outdoor firmly inserted to the terminal block? Is the connecting wiring of indoor and outdoor fixed?
Product (“Defective Parts”) for a period of 5 years from the Date of Purchase. From the date of the GE Appliances will provide new or refurbished parts, or a replacement for all or part of the unit, at its original purchase sole discretion, to your licensed HVAC technician installer.
Página 23
Canada. This warranty it provided by GE Appliances a Haier company, Louisville, KY 40225. ATTACHMENT 1 The product is defined as product sold by GE Appliances, a Haier Company. The product containers 2 sub-categories of goods, indoor and outdoor products, which are defined as AUH**, AHY**, UUH**, UUY***, UUC**, UUH*...
Página 24
Instructions Unité de traitement d’air d’installation Le fabricant recommande d’installer un système intérieur et extérieur assorti répertorié AHRI. LISEZ ET CONSERVEZ CES L’installation d’un système intérieur et extérieur apparié approuvé fournira une efficacité optimale et INSTRUCTIONS la meilleure fiabilité globale du système. 31-5000486 Rev.
Renseignements De Référence Merci d’acheter ce produit GE Appliances. Ce manuel d’utilisation _______________________________________ vous aidera à obtenir le meilleur rendement de votre nouveau Numéro de modèle climatiseur. _______________________________________ Pour référence ultérieure, inscrivez les numéros de modèle et de Numéro de série série sur l’étiquette située sur le côté...
CONSIGNES DE SÉCURITÉ IMPORTANTES LISEZ TOUTES LES INSTRUCTIONS AVANT D’UTILISER LE SYSTÈME AVERTISSEMENT Pour votre sécurité, les renseignements dans ce manuel doivent être observés afin de minimiser le risque d’incendie, de décharge électrique ou de blessure. Les règlements fédéraux exigent qu’un technicien •...
Página 27
CONSIGNES DE SÉCURITÉ IMPORTANTES LISEZ TOUTES LES INSTRUCTIONS AVANT D’UTILISER LE SYSTÈME La réglementation relative aux câbles et aux disjoncteurs diffère ATTENTION selon les régions, il faut donc respecter les codes locaux. Il est fortement recommandé de ne N’utilisez pas les conduites de réfrigérant existantes. pas ouvrir ou fermer les robinets d’arrêt lorsque la température extérieure est en dessous de -5 °F (-21 °C) car cela pourrait Utilisez une tuyauterie de réfrigérant qui est propre et exempte...
à autre. Tout le travail doit être réalisé par des personnes formés, 8. GE Appliances n’assume aucune responsabilité pour expérimentées et agréées dans les domaines mécanique les blessures, les pertes de propriété ou les dommages et électrique.
Instructions d’installation Outils nécessaires pour l’installation • Câble de thermostat 18-8. • Microvacuomètre • Clé 5/8 (16 mm), 7/8 (22 mm), 1 po (25 mm) ou • Adaptateur « mini-split » (5/16 po F à 1/4 po M) réglable • Azote* •...
Instructions d’installation Dimensions de l’unité Dimension en pouces (mm) Modèle Largeur Profondeur Hauteur UUY24ZGDA* 21-1/4(540) 21-1/4(540) 48-1/4(1224) 11-5/8(295) 20(508) UUY36ZGDA* UUY48ZGDA* 24-3/4(630) 21-1/4(540) 57(1448) 11-5/8(295) 20(508) UUY60ZGDA* Dégagements pour l’installation Un dégagement de 24 po est nécessaire pour le retrait du filtre, du serpentin ou du ventilateur et l’accès de service.
Assembly Blower Wheel Fan Motor Secondary Drain Pan Evaporator Assembly Primary Drain Pan Modèle Capacité de Élément chauffant en option refroidissement (kW) (tonne) UUY24ZGDA* 5/8/10 UUY36ZGDA* 5/8/10 UUY48ZGDA* 10/15/20 UUY60ZGDA* 10/15/20 Modèle Motor @ 230V ~, 60Hz UUY24ZGDA* UUY36ZGDA* UUY48ZGDA* UUY60ZGDA* Modèle...
Página 32
Instructions d’installation ATTENTION AVERTISSEMENT Avant l’installation, coupez toutes les sources • Cette unité de traitement d’air est conçue pour une d’alimentation électrique destinées à l’utilisation de cet installation à l’intérieur seulement. N’installez pas équipement. cette unité à l’extérieur. • Lorsque vous installez l’unité de traitement d’air, 1.
Página 33
Diamètre extérieur (pouces) IMPORTANT: Tuyau de gaz Tuyau de liquide • Les tuyaux de réfrigérant de connexion doivent être UUY24ZGDA* propres, déshydratés, fabriqués d’un cuivre de qualité UUY36ZGDA* réfrigérant. Les serpentins de l’unité de traitement d’air UUY48ZGDA* doivent être installés seulement avec des dimensions UUY60ZGDA* de tuyaux spécifiées pour des combinaisons de...
Página 34
Instructions d’installation Installation du dispositif d’évacuation Installation du dispositif d’évacuation du condensat du condensat (suite) Des raccords de tuyaux d’évacuation du condensat 3/4 po NPT 1. Versez plusieurs litres d’eau dans le plateau à sont fournis avec l’unité de traitement d’air. condensat, suffisamment pour remplir le siphon et le tuyau.
Instructions d’installation Exigences électriques Modèle Alimentation Calibre de disjoncteur recommandé (A) UUY24ZGDA* UUY36ZGDA* 208/230V-1Ph-60Hz UUY48ZGDA* UUY60ZGDA* Câblage de commande à câblage électrique Connexions du câblage Utilisation d’un câble en cuivre à âme solide, calibre 18 1. Les câbles de haute et basse tension doivent être acheminés à...
Instructions d’installation Trousse d’élément chauffant Connexions électriques 1. Reportez-vous au tableau pour la trousse d’élément Connect to 5/810kw heater Circuit Breaker chauffant qui convient. Air Handler Supply Voltage 2. Vérifiez que la trousse d’élément chauffant ne comporte aucun dommage physique; n’installez pas une trousse Wire Connections d’élément chauffant endommagée.
Página 37
Instructions d’installation Détendeur thermostatique (ang. TXV) Détendeur thermostatique installé à l’usine Les ampoules sensibles sont installées à l’usine et fixées au tuyau d’aspiration. Pour obtenir une performance optimale, réinstallez et isolez le bulbe à la position de 10 h ou 2 h à l’extérieur du boitier vers la conduite d’aspiration principale et à...
Página 38
Instructions d’installation Connexions du thermostat Thermostat Connections REMARQUE : Y signifie le signal de commande du compresseur de l’appareil extérieur; NOTE: Y means Compressor control signal for the outdoor unit; B étant sous tension en mode de chauffage signifie le signal B which is energized under the heating mode means 4-way valve control signal;...
Página 39
Instructions d’installation Indoor unit Power CB1CB2 CB2 CB1 HEAT HEAT 2 3 4 5 6 Code Name ② Circuit breaker only Code Name for 10KW heat kit Circuit breaker Circuit breaker only 10KW HEAT KIT 15KW/20KW HEAT KIT for 5/10KW heat kit X1 X2 Tube W6 W7...
Página 40
Instructions d’installation Instructions de réglage du débit d’air pour la série Connect Les réglages de débit d’air de l’appareil de traitement d’air sont au niveau 4. Le débit d’air peut être réglé en utilisant les commutateurs DIP du tableau de commande de différentes vitesses selon la pression statique du système. Les paramètres de vitesses de ventilateur sont indiqués ci-dessous : 1.
Página 41
Instructions d’installation Instructions de réglage du débit d’air pour la série Connect Configuration des commutateurs DIP Modèle Niveau Chauffage (SA2) Climatisation (SA1) Niveau 1 Niveau 2 Niveau 3 Niveau 4 - Défaut UUY24ZGDAB Niveau 5 Niveau 6 Niveau 7 Niveau 8 Niveau 1 Niveau 2 Niveau 3...
Página 42
Instructions d’installation Instructions de réglage du débit d’air pour la série Connect Données de performance du ventilateur Model Static 0.15 Pressure- Inches W.C. UUY24ZGDAB 1030 Niveau 1 1080 Niveau 2 1120 1060 Niveau 3 1240 1180 1070 Niveau 4 1390 1290 1180 1090 970...
Página 43
Instructions d’installation Vérification finale Point à vérifier pour l’application du test Mise à l’essai du système Veuillez expliquer au client comment piloter le système Aucune fuite de gaz dans la tuyauterie? à l’aide du manuel d’utilisation qui accompagne l’unité La tuyauterie est-elle isolée correctement? intérieure.
Cette garantie couvre tous les vices de matière et de fabrication des pièces mécaniques et électriques contenues dans le Produit (« Pièces défectueuses ») durant une période de cinq (5) ans à partir de la Date d’achat. GE Appliances sur les pièces fournira des pièces neuves ou réusinées ou, à...
Página 45
à vous. Cette garantie vous accorde des droits particuliers et il peut exister d’autres droits qui varient selon l’État ou la province. Cette garantie couvre les appareils dans les cinquante (50) États des États-Unis, du district de Columbia ou du Canada Cette garantie est attribuée par GE Appliances a Haier company, Louisville, KY 40225.
INSTRUCCIONES Climatizador DE INSTALACIÓN El fabricante recomienda instalar un sistema de interior y exterior combinado homologado por AHRI. LEA Y GUARDE ESTAS La instalación de un sistema homologado para INSTRUCCIONES interiores y exteriores proporcionará una eficiencia óptima y la mejor confiabilidad general del sistema. 31-5000486 Rev.
Mantenimiento De Registros Gracias por adquirir este producto de GE Appliances. Este manual del propietario le ayudará a lograr el mejor rendimiento de su nuevo _____________________________________ acondicionador de aire. Número de modelo Para referencia futura, registre el modelo y número de serie ubicados en la etiqueta que se encuentra al costado de su acondicionador de aire, y la fecha de compra.
Página 48
INFORMACIÓN IMPORTANTE DE SEGURIDAD LEA Y GUARDE ESTAS INSTRUCCIONES ADVERTENCIA Para su seguridad, siga las instrucciones de este manual a fin de minimizar riesgos de incendio, descargas eléctricas o lesiones personales. • Use este equipo sólo para su propósito original, como se Las regulaciones federales requieren que un técnico describe en el Manual del Usuario.
Página 49
INFORMACIÓN IMPORTANTE DE SEGURIDAD LEA Y GUARDE ESTAS INSTRUCCIONES PRECAUCIÓN La regulación de cables y disyuntores difiere de acuerdo a cada localidad; consulte en relación a las reglas locales. Se recomienda encarecidamente que no abra ni cierre las No use las tuberías de refrigerante existentes. válvulas de cierre cuando la temperatura exterior sea inferior a -5 °...
Es responsabilidad del instalador asegurar que todos los 6. Si el producto funciona mal y/o no funciona, por aspectos de la instalación de este producto se adhieran a favor comuníquese con el soporte técnico de GE los códigos nacional, estatal y local. Appliances. Brinde la siguiente información: No es posible tratar en este manual cada diferencia a.
Instrucciones de Instalación Herramientas Requeridas para la Instalación • Cable del termostato de 18-8 • Medidor de micrones • 5/8” (16mm), 7/8” (22mm), 1” (25mm) o llave ajustable • Adaptador para mini split (5/16”F a 1/4”M) • Refrigerante R-410A* • Nitrógeno* •...
Instrucciones de Instalación Dimensiones de la Unidad Dimensión en pulgadas (mm) Modelo Ancho Profundidad Altura UUY24ZGDA* 21-1/4(540) 21-1/4(540) 48-1/4(1224) 11-5/8(295) 20(508) UUY36ZGDA* UUY48ZGDA* 24-3/4(630) 21-1/4(540) 57(1448) 11-5/8(295) 20(508) UUY60ZGDA* Espacios Libres de la Instalación Se requiere un espacio libre de 24” para el retiro y acceso al servicio del filtro, bobina o soplador.
Control Box Assembly Blower Wheel Fan Motor Secondary Drain Pan Evaporator Assembly Primary Drain Pan Modelo Capacidad de Calentador eléctrico opcional enfriamiento (ton) (kW) UUY24ZGDA* 5/8/10 UUY36ZGDA* 5/8/10 UUY48ZGDA* 10/15/20 UUY60ZGDA* 10/15/20 Modelo Motor @ 230V ~, 60Hz UUY24ZGDA* UUY36ZGDA* UUY48ZGDA*...
Página 54
Instrucciones de Instalación PRECAUCIÓN ADVERTENCIA • Este climatizador fue diseñado para la instalación en Antes de la instalación, apague todos los suministros interior únicamente. No lo instale en áreas exteriores. de corriente eléctrica que se utilizan con este equipamiento. • Al instalar el climatizador, tenga en consideración minimizar la longitud de la tubería de refrigerante tanto como sea posible.
Diámetro Exterior (pulgadas) EPA, de acuerdo con los procedimientos establecidos. Tubería de gas Tubería de líquido IMPORTANT: UUY24ZGDA* • Las tuberías de refrigerante conectadas deberán UUY36ZGDA* ser tuberías de cobre limpias, deshidratadas y con UUY48ZGDA* calificación para uso con refrigerante. Las bobinas del UUY60ZGDA* climatizador se deberán instalar sólo con los tamaños de...
Instrucciones de Instalación Instale el Drenaje de Condensados Instale el Drenaje de Condensados (cont.) El climatizador se entrega con conexiones de drenaje de condensados NPT de 3/4”. 1. Vierta varios cuartos de galón de agua en la bandeja Se requiere una bandeja de drenaje secundaria producida de drenaje, de modo que sea suficiente para llenar el en fábrica con una tubería de drenaje hacia el exterior de colector de drenaje y la tubería.
Instrucciones de Instalación Requisitos Eléctricos Modelo Suministro de Corriente Tamaño recomendado del disyuntor (A) UUY24ZGDA* UUY36ZGDA* 208/230V-1Ph-60Hz UUY48ZGDA* UUY60ZGDA* “Cableado del control” al “Cableado eléctrico” Conexiones del Cableado 1. Los cables con niveles de voltaje altos y bajos se Uso de un Cable de Cobre del Núcleo Sólido Calibre 18 deberán conducir a través de diferentes anillos de...
Instrucciones de Instalación Conexiones Eléctricas Kit del Calefactor 1. Consulte en la tabla el kit del calefactor correspondiente. Connect to 5/810kw heater Circuit Breaker 2. Controle que no posea ningún daño físico; no instale un kit Air Handler Supply Voltage de calefactor dañado.
Instrucciones de Instalación Válvula de Expansión Térmica (TXV) Válvulas de Expansión Instaladas de Fábrica: Las lámparas con sensor se encuentran instaladas de fábrica y están sujetadas a la tubería de succión. Para un rendimiento óptimo, vuelva a adherir y aísle la lámpara en una posición de las 10 o 2 en punto fuera del gabinete hasta la tubería de succión principal, a no más de un pie desde la conexión de la tubería de...
Página 60
Instrucciones de Instalación Thermostat Connections NOTA: Y se refiere a la señal de control del Compresor para la unidad exterior; Conexiones del Termostato B que es alimentado en el modo de calefacción, se refiere a la señal de control NOTE: Y means Compressor control signal for the outdoor unit; de la válvula de 4 vías;...
Página 61
Instrucciones de Instalación Unidad interior – 5/9 de ton Indoor unit Encendido Power CB1CB2 CB2 CB1 HEAT HEAT 2 3 4 5 6 Code Name ② Circuit breaker only Code Name for 10KW heat kit Circuit breaker Circuit breaker only 10KW HEAT KIT 15KW/20KW HEAT KIT for 5/10KW heat kit...
Página 62
Instrucciones de Instalación Instrucciones de Ajuste del Flujo de Aire para la Serie Connect Las configuraciones para la circulación de aire por omisión del climatizador son de Nivel 4. El flujo de aire se podrá ajustar usando diferentes velocidades en los interruptores DIP del tablero de control, de acuerdo con la presión estática del sistema.
Página 63
Instrucciones de Instalación Instrucciones de Ajuste del Flujo de Aire para la Serie Connect Configuración del interruptor DIP Modelo Nivel Calor (SA2) Frio (SA1) Nivel Nivel Nivel Nivel Défaut UUY24ZGDAB Nivel Nivel Nivel Nivel Nivel Nivel Nivel Nivel Défaut UUY36ZGDAB Nivel Nivel Nivel...
Página 64
Instrucciones de Instalación Instrucciones de Ajuste del Flujo de Aire para la Serie Connect Datos de rendimiento del soplador Model Static 0.15 Pressure- Inches W.C. UUY24ZGDAB 1030 Nivel 1 1080 Nivel 2 1120 1060 Nivel 3 1240 1180 1070 Nivel 4 1390 1290 1180...
Instrucciones de Instalación Control Final Prueba del Sistema Controle los Ítems para la Prueba de Funcionamiento Por favor, explíquele al cliente cómo utilizar el sistema usando el Manual del Propietario, el cual se encuentra con la unidad de interior. ¿No hay pérdida de gas del conjunto de tuberías? ¿Está...
Garantía del compresor de 7 El compresor perteneciente a este producto posee garantía por un período de 7 años desde la Fecha de Compra. GE años a partir de la fecha de la Appliances le proveerá...
Página 67
ADJUNTO 1: El producto se define como el producto vendido por GE Appliances, una empresa Haier. El producto contiene 2 subcategorías de productos, productos para interiores y exteriores, que se definen como AUH **, AHY **, UUH **, UUY ***, UUC **, UUH *...