19
PWM standard version
(heating standard)
Multitherm version
Pump for optimum heat
distribution control
via special speed control
(PWM)
english
4. PWM [81] [82]
Connection: Clamp 81: PWM +
Clamp 82: PWM –
The control module offers the option of using
an external speed target value specification
with 2 different PWM models.
The following setting can be made here on the key (1):
PWM standard LED (2) flashing
In PWM standard operation, the pump is controlled
via an external PWM signal.
PWM multitherm, LED (3) flashing
In PWM multitherm operation, the pump is controlled
via an external multitherm signal.
Frequency
High voltage
Low voltage
PWM signal
0 ... 10%
11 ... 84%
84 ... 91%
91 ... 95%
95 ... 100%
Frequency
High voltage
Low voltage
PWM signal
0%
2 ... 3%
7 ... 93%
93 ... 95%
In the event of a fault the input signal is short-circuited
50 ... 4000 Hz
4.5 ... 24 V
0 ... 0.5 V
Speed
max. speed
linear speed specification
min.
Hysteresis range – on/off
Standby (OFF)
70 ... 300 Hz
8 ... 15 V
0 ... 0.5 V
Speed
max.
off
min. ... max.
max.