HSM3350 v1.0 Power Supply Module Installation Instructions
Power Supply
The HSM3350 is a supervised 3 A 12 VDC power supply module with dual AUX outputs
and dual battery backups, which is compatible with the PowerSeries Pro panels.
General
This product meets the requirements of Class II, Grade 3 equipment as specified by
EN50131-1:2006 + A1:2009, + A:2:2017, EN50131-3:2009 Type B, EN50131-6:2017 Type
A.
Specifications
Power supply Type A as per EN50131-6 Standard.
l
Temperature range: - 10°C to + 55°C (14°F to 131°F); UL/ULC verified operation
l
range: 0 °C to + 49°C (32°F to 122°F).
Relative Humidity: 5% to 93% R.H. non-condensing.
l
HS65WPSx Supply Ratings: Input 100 V-240 VAC 50/60 Hz Max 1.7 A. Output 18
l
VDC 3.6 A Max. Only one board can be powered from a HS65WPSx. Where x = NA
for UL/ULC cord connected, NAS for UL/ULC hardwired applications, and none for
CE/EN compliant installations.
Note: For EU (CE/EN50131 compliant installations) use the power adapter model
HS65WPS. Mount the power adapter model inside the cabinet with a fuse block and per-
manently connect it to the module. To replace the fuse, use the same type (20 mm) rated
250 V / 3.15 A slow blow.
Note: For UL/ULC installations, use the power adapter model HS65WPSNA mounted
inside or outside the HSM3204CX enclosure. Do not connect the power supply adapter to
receptacle controlled by a switch.
Board current draw: 35 mA (set and unset state/alarm and non-alarm state)
l
Board dimensions: 190 mm x 96.5 mm (7.5 in x 3.8 in)
l
AUX output ratings: 10.8 -12.5 VDC - 15% -+ 10% / 3 A max
l
Output ripple voltage: 600 mVp- p max
l
No overvoltage protection devices required on the outputs
l
Storage device: rechargeable battery, rated 12 VDC. Replace battery every 3 to 5
l
years
Battery capacity: 4 Ah, 7 Ah, or 14 Ah (2 x 7 Ah), 17 Ah or 18 Ah, 34 Ah (2 x 17 Ah),
l
36 Ah (2 x18 Ah) max.
Note: Use 18 Ah batteries only for NFA2P certified installations.
Low battery trouble indication threshold 11.6 VDC, restoral level 12.5 VDC
l
Corbus (RED terminal) low voltage trouble threshold 6 VDC
l
Battery deep discharge protection (cut- off at 9.2 VDC)
l
The hardware is ROHS compliant
l
The design has an RF Immunity of 10 V/M
l
This equipment must be installed by skilled service persons in non-hazardous, indoor
l
locations. The equipment is unsuitable for use outside the supervised premises.
The voltage at any independent power output below which the power output fault sig-
l
nal or message will be generated : 9.8 Vdc
Over-voltage protection trigger voltage 16.5 VDC
l
The storage device (standby battery) does not automatically recharge when recon-
l
nected to the AC mains (EPS), if the battery terminal voltage is less than 9.6 VDC.
The minimum energy level of the SD in its charged state (as a percentage of the SD
l
rated capacity for the range of SDs that can be used with the PS) is 90% (for 17Ah or
34Ah (2 x 17 Ah) batteries).
Note:
For EN50131-6: 2008 grade 2 compliant installations, use one 12 V / 17 Ah battery or
l
two 12 V/17 Ah batteries (BAT2 must be enabled) for 12 h of required standby time
(1200 mA or 2400 mA output current). Recharge time to 80% is 72 h. Supervision for
loss of primary power source (AC Fail), battery fail, or battery low voltage (Battery
Trouble) with indication on the keypad.
For EN50131-6: 2008 Grade 3 compliant installations, use one 12 V / 17 Ah battery or
l
two 12 V/17 Ah batteries (BAT2 must be enabled) for 30 h/60 h of required standby
time (500 mA / 250mA or 1000 / 500 mA output current). Recharge time to 80% is 24
h. The charging current must be set to high.
For T014 (INCERT) compliant installations, use two 12 V / 17 Ah batteries for 24 h of
l
required standby time (1200 mA output current) and the enclosure model HSC3020C
(INCERT certified). The charging current must be set to high.
Table 1 : Compatibility
Panel compatibility
HS3032, HS3128
Enclosure compatibility
HSC3010C, HSC3010CR, HSC3030CAR, HSC3020C
Connectivity compatibility
Corbus
Terminal Descriptions
Figure 1: Terminal descriptions
Table: 2 Terminal details
UL/ULC applications: 120 VAC/60 Hz 1.7 A (cord connected)
Primary Input
CE/EN50131 applications: 230 VAC/50 Hz 1.7 A (hardwired)
Corbus
Connects to the main control panel communication bus (HS3032, HS3128)
N.C. Tamper
To remove the door or cover, or to remove from mounting location, con-
Contact
nect N.C. tamper contact to tamper switch installed in the cabinet
AUX output
Shared with Corbus. Ratings: 10.8 VDC - 12.5 VDC / 3 A max. Supervised
Note:
Fire and Security devices that require power from the HSM3350 must be UL/ULC Lis-
l
ted for the intended application and operate over the range 10.5 Vdc - 12.5Vdc.
All circuits are classified for Ul installations as power limited/Class II power limited,
l
except for the battery leads which are not power limited.
Do not route any wiring over circuit boards. Maintain at least 1" (25.4 mm) separation.
l
A minimum of 1/4" (6.4 mm) separation must be maintained at all points between
l
power limited wiring and all other non- power limited wiring.
Inspect wiring and ensure connections are correct before applying power.
l
Refer to the Installation Manual for proper selection of battery capacity based on the
l
intended application and maximum loading allowed.
BAT 2 must be enabled in programming.
l
Table 3: Switching Mode Power Adapter
Primary
Model
Listed Installation
Enclosure
Connection
Input
120
HSC3010C
Cord
VAC/50
(inside /out-
HS65WPSNA
UL/ULC
connected to
HZ/1.7 A
side)
AC mains
Max
HSC3010CR
120
ULC Commercial Fire, ULC
HSC3010C
Hardwired
VAC/50
HS65WPSNAS
Commercial Burg Security
(Inside, use high
connection to
HZ / 1.7
Level IV
voltage barrier
AC mains
A Max
kit)
230
Hardwired
VAC/60
HS65WPS
CE/EN50131
HSC3020C
connection to
HZ / 1.7
AC mains
A Max
Table 4 : Ratings
UL R esi Fire
UL R esi Fire
HSM3350
UL,HH, ULC
with wired C O
PC B cur-
UL R esiB urg
UL C OM
UL C OM
EN50131
R esiFire
Detectors
rentdraw =
ULC R esiB urg
B urg
firemonitoring
Grade 2
ULC C om
UL985 6th Ed
35 mA
B urg
29010128R001
Standby
24 h + 4 min
24 h + 4 min
4 h + 4 min
time and
4 h + 15 min
24 h + 5 min
+12h C O
4 h + 5 min
24 h + 4 min
Alarm
alarm time
HSC 3010C
HSC 3020C
Enclosure
HSC 3010C
HSC3030CAR
HSC 3010C
(ULC C B )
HS65WPSNA
HS65WPSNAS
(ULC  C B
Power
Security Level
supply
HS65WPSNA
HS65WPSNA
HS65WPSNA HS65WPSNAS
4)
(R equire high
adapter
voltage barrier
kit)
B attery
4 Ah/700m A
4 Ah/700 m A
14 Ah /500m A
14 Ah /330m A
capcity
7 Ah/1200 m A
7 Ah/1200 m A
17 Ah /600m A
17 Ah /400m A
/max
14 Ah/3000 m A
14 Ah/3000 m A
34 Ah/1200 m A
34 Ah/800 m A
17 Ah/3000 m A
17 Ah/3000 m A
loading
R echarging
Low (400 mA)
Low (400 mA)
High (700
current
for 4Ah High
for 4Ah High
High (700 mA)
mA)
setting
(700 mA)
(700 mA)
DC -
Supervised, the HSM3350 requires 18 VDC/3.6 A power supply module. Connect the
.
primary of the power supply module to an unswitched AC source (maximum current draw
is 1.7 A) and connect the secondary of the power supply module (US market only) to these
.
terminals.
.
TAM-
Used to tamper protect the cabinet in which the HSM3350 is mounted. Connect a
normally closed (NC) switch across +TAM and -BLK. If the tamper is not being used con-
.
nect a piece of wire across + TAM and - TAM to remove the trouble condition. Tamper
.
protect is required for UL/ULC/EN commercial/residential burglary installations.
AUX1 -
Used to provide power for devices. Maximum current draw is not to exceed
3000 mA. Connect the positive lead of powered devices to +AUX1 and the negative to -
AUX1 .
AUX2 -
Used to provide power for devices. Maximum current draw is not to exceed
3000 mA. Connect the positive lead of powered devices to +AUX2 and the negative to -
AUX2 .
CORBUS -
The 4-wire Corbus connection is used by the panel to communicate with the
module. Connect the RED, BLK, YEL and GRN terminals to the Corbus terminals on the
HS2032 or HS3128 main control.
Note: AUX 1 and AUX 2 can individually provide a current draw of up to 3 A. The com-
bined output on both AUX 1 plus AUX 2 is also 3 A. Do not exceed this amount or the out-
puts self- protect and switch off.
Note: The HSM3350 is not suitable for fire alarm annunciation
Enclosures
Output
The HSM3350 can be installed in the metal enclosures listed below. Tamper protection
switches can be installed on all enclosures, including door opening protection and/or
18 VDC/3.6
removal from the mounting position. Doors are secured using screws or keylock.
A Max
Powerseries Pro enclosures :
Model HSC3010C (hinged door) made of 18 Ga steel, painted white, dimensions 372
l
mm x 412 mm x 114 mm, weight: 9.75 lb or 4.2 Kg
Model HSC3010CR (hinged door) made of 18 Ga steel, painted red, dimensions 372
l
18
mm x 412 mm x 114 mm, weight: 10.0 lb or 4.5 Kg
VDC/3.6
Model HSC3030CAR (hinged door) made of 18 Ga steel (base) and 16 Ga (door),
l
A Max
painted white, dimensions 375 mm x 412 mm x 114 mm, weight: 11.45 lb or 5.2 Kg
Model HSC3020C (removable door) made of 18 Ga steel, painted white, dimensions
l
459 mm x 414 mm x 103 mm, weight: 4.3 Kg (no batteries)/12Kg (17Ah/18Kg (34 Ah)
18
Note: Refer to HS3128/HS3032 Reference Manual for details of mounting locations of the
VDC/3.6
power supply board for compatible cabinets.
A Max
Battery Setting
A battery charge current setting in the panel is used to enable high charge current for the
battery. Normally the battery charge current can be 400 mA max, but when this option is
enabled the module can charge the battery with up to 700 mA of current. Section [982]
[040] Options 1and 2 can enable or disable the high current batteries 1 and 2 charge option
for HSM3350 modules. Option 3 in this section is used to enable or disable battery 2.
En50131
Grade3
Status LED
30 h
(AC fail
The HSM3350 are equipped with status LEDs to indicate the current status of the module.
24 h + 30 min
12 h
transmission
If the HSM3350 is operating correctly, the status LED flashes briefly every 10 seconds.
required)
When a trouble condition is present, the status LED displays a series of flashes and remains
60 h
blank for 2 seconds. The number of flashes between blank periods indicates the trouble
condition present as outlined in Table 2.
Table 5 : Trouble Conditions
HSC3010CR
HSC3020C
HSC 3020C
Number of Flashes
Trouble Condition
1
Module not enrolled
2
Panel supervision trouble
3
Corbus low voltage
HS65WPS
HS65WPS
4
5
6
17 Ah/500 m A
14 Ah/500 m A
17 Ah /1200 m A
34 Ah/1000 m A
Enroll Modules
17 Ah/600 m A
34 Ah/2400 m A
17 Ah/250 m A
1.
Enter Installer Programming [*] [8][Installer Code] [*].
34 Ah/1200 m A
34 Ah/500 m A
2.
Enter section [902] to enroll the module. Modules can be enrolled automatically or
manually. In either case, the serial number of the device is used as an identifier. Select
High (700
one of the enrollment options described below:
High (700 mA)
Low (400mA)
mA)
000 Auto Enroll
When this mode is selected, the total number of modules currently enrolled are displayed
on the keypad.
1.
After entering subsection [000], press the [*] key to begin auto enrollment of all new
modules. Devices are assigned in numerical order.
001 Manual Enroll
1.
After entering Installer Programming and section [902], enter subsection 001.
2.
When prompted, key in the serial number of the module, which is found on the back of
the device. An error tone is sounded if an invalid serial number is received. Modules
are enrolled into the next available slot for the device.
3.
To cancel enrollment of a module, press [#].
Deleting Modules
1.
Enter Installer Programming [*] [8][Installer Code] [*].
2.
Enter section [902] then subsection [111] for HSM3350.
3.
Scroll to the specific module you want to delete.
4.
Press [*] to select the module then, when prompted, press [*] again to delete.
Confirming Modules
To confirm enrollment of individual modules and to locate them physically complete the fol-
lowing steps:
1.
After entering section [903], scroll to the module type you want to confirm (111 for
HSM3350). To view all modules, enter [000] after entering section [903].
2.
Press [*] to select the module type then scroll to the specific module you want to con-
firm.
3.
Press [*] to enter confirmation mode. The module's serial number and slot number are
displayed on the keypad and the status LEDs on the device flash. This continues until
confirmation mode for the device is exited using the [#] key.
Mounting
1.
Install the wire through the wall for mounting.
2.
Attach the mounting bracket to the wall in the position you want with mounting hard-
ware. If mounting on drywall, mark the four installation points, remove the mounting
plate and install the drywall inserts.
3.
Insert the module into the mounting braket.
4.
Fasten the module to the mounting bracket.
Limited Warranty
DigitalSecurity Controls (DSC) warrants that for aperiodof twelve monthsfrom thedate of purchase, theproduct shall befree of defects inmaterials andwork-
manshipunder normal useandthat infulfillment of anybreach of such warranty, DSCshall, at its option,repair or replace the defective equipment uponreturn of
theequipment toits factory. Thiswarranty applies onlyto defectsin partsand workmanshipandnot todamage incurred inshipping or handling, or damagedue to
causesbeyond thecontrol of DSC suchas lightning, excessive voltage, mechanical shock, water damage, or damage arising out of abuse,alterationor improper
applicationof theequipment.
Theforegoing warranty shallapply only totheoriginal buyer, andis andshall beinlieu of anyand allother warranties, whether expressed or implied andof allother
obligations or liabilities on thepart of DSC.This warranty contains theentire warranty. Digital SecurityControls neither assumes responsibility for,nor author-
izesanyother person purportingtoact onits behalf tomodify or to changethis warranty, nor to assumefor it anyother warranty or liability concerningthis
product.In noevent shallDSC beliable for any direct or indirect or consequentialdamages, loss of anticipatedprofits, loss of timeor anyother lossesincurred by
thebuyer inconnectionwiththe purchase, installationor operation or failure of thisproduct.
Warning:Digital Security Controls recommends that theentire system be completelytested onaregular basis. However, despitefrequent testing, and dueto,but
not limited to,criminal tampering or electrical disruption, it is possible for thisproduct tofail toperform as expected.
IMPORTANT - READ CAREFULLY: DSC Software purchased withor without Products and Components is copyrightedand is purchased under thefollowing license
terms:
ThisEnd-User License Agreement ("EULA") is alegal agreement between You(the company,individual or entity whoacquired theSoftware and anyrelated Hard-
ware)and DigitalSecurity Controls, adivision of TycoSafety Products Canada Ltd.("DSC"), themanufacturer of theintegratedsecurity systems and thedeveloper
of thesoftware and anyrelated products or components ("HARDWARE")which Youacquired. If theDSC softwareproduct ("SOFTWARE PRODUCT" or
"SOFTWARE") is intended tobe accompaniedbyHARDWARE, andis NOTaccompaniedby newHARDWARE, You maynot use, copyor install theSOFTWARE PRODUCT.
TheSOFTWARE PRODUCT includes computersoftware, and mayinclude associatedmedia, printed materials, and"online" or electronic documentation.Anysoft-
wareprovided along withtheSOFTWARE PRODUCT that is associatedwith aseparate end-user licenseagreement is licensed toYouunder theterms of that license
agreement.
Byinstalling, copying, downloading,storing, accessing or otherwise using the SOFTWAREPRODUCT, You agreeunconditionally tobe boundbythe terms of thisEULA,
evenif this EULA is deemedto beamodificationof anyprevious arrangement or contract. If Youdo not agree totheterms of this EULA,DSC is unwilling to
licensethe SOFTWARE PRODUCTto You,and Youhave noright touseit.
©2018 Tyco Security Products www.dsc.com
Tech. Support: 1-800-387-3630
Battery trouble
AC trouble
AUX trouble

Publicidad

loading

Resumen de contenidos para Johnson Controls Tyco HSM3350

  • Página 1 Terminal Descriptions Status LED 30 h Standby 24 h + 4 min (AC fail The HSM3350 are equipped with status LEDs to indicate the current status of the module. 24 h + 4 min HSM3350 v1.0 Power Supply Module Installation Instructions 4 h + 4 min time and 4 h + 15 min...
  • Página 2 SOFTWARE PRODUCT LICENSE Pour l’UE (installations conformes CE/EN50131), utilisez le module d’adaptateur d’ali- Figure 1: Descriptions des bornes (ULC C B ) TheSOFTWARE PRODUCT is protected bycopyright laws andinternational copyright treaties, as wellas other intellectual property lawsandtreaties. The mentation HS65WPS. Montez le modèle d’adaptateur d’alimentation à l’intérieur de Table 2 : Détails des bornes SOFTWAREPRODUCT is licensed, not sold.
  • Página 3: Especificaciones

    Avertissement :Digital Security Controls recommandequela totalitédu système soit testé régulièrement.Toutefois, même sivous faitesdes testspériodiques, notements puis reste éteint pendant 2 secondes. Le nombre de clignotements entre les péri- General Descripciones del terminal ilpeut arriver que lefonctionnement du produit ne soit pas conforme auxspécifications enraison notamment, maispas exclusivement,d’interventions criminelles odes à...
  • Página 4: Montaje

    Modelo HSC3020C (puerta desmontable) en acero calibre 18, color blanco, dimen- Montaje ES Certificación ElMódulo deHSM3350 hasidocertificado por CERTALARM Teleficationde acuerdo conEN50131- 1:2006+ A1:2009+ A2:2017y EN50131-6:2017 para Grado 3, ClaseII siones 459 mm x 414 mm x 103 mm, peso: 4.3 Kg (sin pilas) / 12 Kg (17 Ah / 18 Kg Instale el cable a través de la pared para el montaje.
  • Página 5 responsabilidadereferente aeste produto. Em nenhum casoserá aDSC responsável por qualquer dano direto,indireto ou consequencial,por perdadelucros ante- Descrições dos terminais máximo 400mA, mas quando essa opção for ativada, o módulo poderá carregar a bateria R oubo C om. UL985 6th Ed cipados,perda detempo ouqualquer outra perdaincorrida pelo comprador em relação àcompra, instalaçãooufuncionamento desteproduto.