PS-630E
Power Manager 
BATTERY LOW LED: it lights up in yellow, as a warning, if the battery voltage sinks below approx. 
20.0  VDC  in  an  emergency  power case. The emergency  power  ends  at  battery  voltage  of approx. 
18.0 V. The total discharge protection then separates all consumer outputs from the battery. 
 
BATTERT FAIL LED: it lights up in yellow after approx. 1 minute after power on, If the battery and 
the  battery  circuit  (including  internal  and  external  cell  connectors  and  fuse)  are  too  high  in 
impedance (over 0.1 Ohm). The fault will be reported via the dry contact signal pin7~9, pin7, pin8 
become short circuit. 
 
Relay Dry Contact pin assignment 
 
CHARGER / AC IN: 
1 = Normally Closed 
2 = Common 
3 = Normally Open 
In fault condition 1‐2 become open circuit. 
 
CONTROLLER OK: 
4 = Normally Closed 
5 = Common 
6 = Normally Open 
In fault condition 4‐5 become open circuit. 
 
BATTERY FAIL: 
7 = Normally Closed 
8 = Common 
9 = Normally Open 
In fault condition 7‐8 become short circuit. 
 
Pin assignment for Battery Temperature Sensor and Remote Battery Discharge Test 
 
A / B = Temperature Sensor (sensor is supplied with the PS‐630E) 
 
C / D = Control input for Remote Battery Discharge Test