Installing the Zoneline
6. Level and Secure Drain Platform
1. When installing drain platform, ensure that it is level in all
directions.
Inside Wall
Rigid
Ductwork
Flexible or
Rigid Ductwork
7. Connect the Top Ductwork
1. Use a field supplied clamp to clamp the flexible 10" duct
to the rigid ductwork above the unit.
2. Install the other end of the duct onto the air discharge
outlet. Use a field supplied clamp to secure the duct to
the air discharge outlet.
Inside Wall
Rigid
Ductwork
10"
Flexible or
Rigid Ductwork
20
Air
Discharge
Outlet
10"
Air
Discharge
Outlet
8. Connect the Remote Thermostat
The unit will be controlled by a remote thermostat.
IMPORTANT: The Zoneline thermostat connections provide
24V AC only. If using a digital/electronic wall thermostat,
you must set it to the 24V AC setting. See the Installation
Instructions for the wall thermostat. NOTICE: Damage
to a wall thermostat or to the Zoneline electronics can
result from improper connections. Exercise extra attention
when connecting blue and black wires. No line voltage
connections should be made to any circuit in the thermostat.
Isolate all wires in building from line voltage.
1. Thermostat electrical connector is included with the unit.
Follow the instructions included with the thermostat to
connect the thermostat to the unit.
Thermostat
Maximum Wiring
Length for Thermostat
Connection to the Unit
66 ft. for AWG 18
60 ft. for AWG 20
40 ft. for AWG 24
AWG – American Wire Gauge
Use only Class 2 wiring
2. Plug the thermostat connector into the control board.
Thermostat Connector
7
6 5 4 3 2 1
R
GL
GH
B
Y
W
C
49-5000561 Rev. 1