CSBDSETSAND RECEPTACLES
Use onty high quality, welPinsulated, grounded extension
cords with the generator's 120 Volt electrical receptacles.
Inspect extension cords before each use.
Checkthe ratings of aii extension cords before you use them.
Extensioncord sets used should be rated for 125 Voit AC
loads at 20 Amps or greater for most electrical devices.
Some devices, however, may not require this type of
extension cord. Checkthe operator's manuals of those
devices for the manufacturer's recommendations.
Keepextension cords as short as possible, preferably Iess
than 15 feet iong, to prevent voltage drop and possible
overheating of wires.
WARNING
Overloadedelectrical cords can overheat, arc,
and burn resulting in death, bodily injury, and/or
property damage.
* ONLYusecords ratedfor your loads.
o Followall safetieson ebctricalcords.
128/248 VeJt AC, 38 Amp, Locking Receptacle
Use a NEMA L14-30 piug with this receptacle. Connecta
4-wire cord set rated for 250 Voit AC ioads at 30 Amps (or
greater). You can usethe same 4-wire cord if you plan to
run a 120 Volt load.
4-WheCordSet
J
128 Volt AC, 28 Amp, #uplex Receptacles
Eachduplex receptacle is protected against overload by a
double pole rocker switch circuit breaker.
Use each receptacieto operate 120 Volt AC, singb-phase, 60
Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20
Amps of current. Use cord sets that are rated for 125 Volt AC
loads at 20 Amps (or greater).
BENERAT{)RADAPTER CORD SET
The generator comes with a 25' generator adapter cord set
designedto provide two sets of 120 Voit, 20 Amp outiets
from one 120 Volt, 20 Amp dupiex receptacle.
(Neutral)
Y (Hot)
|
X (Hot)
NEMA L14-30
/-7L7 Ground(Green)
This receptaclepowers 120/240 Volt AC, 60 Hz, single phase
loads requiring up to 5,600 watts of power (5.6 kW) at
23.3 Amps for 240 Volts or two independent 120 Voit ioads
at 23.3 Amps each. The outbt is protected by a double pole
rocker switch circuit breaker.
NOTICE
Receptaclesmay be marked with rating vaiue greater than
generator output capacity.
NEVER attemptto powera devicerequiringrnoreamperage
than generator o r receptacle c ansupply,
DONOT overloadthe generator, S eeDon't Overload Generato,_
The maximum load on each outtet is 20 Amps. The maximum
totai ioad on both biack wire outiets or white stripe wire
outiets is 20 Amps.
NOTE:Foliow aii safety precautions when connecting any
extension cord or device to the generator.
12