Installation

1. Confi gure the Modbus ID (refer to Machine ID Confi guration (SW1) in the Confi guration section for details).
2. Confi gure the communication format (refer to Communication Format Confi guration (SW2) in the Confi guration section
for details).
3. Confi gure the RS-485 resistance (refer to RS-485 Resistance Confi guration (SW3) in the Confi guration section for
details).
4. Insert the MODBUSCARDSV into the UPS accessory slot.
5. Using Cat5e/6 cable with an RJ45 connector, connect the MODBUSCARDSV to a computer (refer to Connection in the
Confi guration section for the details). It is not necessary to turn the UPS off. To connect multiple UPS systems with an
installed MODBUSCARDSV, refer to the instructions in Multiple Monitoring in the Confi guration section.
APPENDIX: Machine ID Confi guration Table (SW1) ✔ = ON, X = OFF
SW1 ID
DIP 1
1
2
×
3
4
×
5
6
×
7
8
×
9
10
×
To confi gure the Modbus ID for additional devices beyond 10, continue with DIP switch ON/OFF by counting in binary
(✔/ON = 1; X/OFF = 0).
19-03-386-93397E.indb 6
19-03-386-93397E.indb 6
DIP 2
DIP 3
DIP 4
×
×
×
×
×
×
×
×
×
×
×
DIP 5
DIP 6
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
6
DIP 7
DIP 8
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
9/12/2019 10:41:54 AM
9/12/2019 10:41:54 AM