5. Jumper Configuration

5.1 Jumper Setup

The 3-pin connectors can be found near the relays.
There are white silkscreens on the connector to indicate Normally Open pins 1 and 2, and Normally Closed pins 2 and 3.
To achieve a Normally Open dry-contact signal, the jumper should
connect to pins 1 and 2.

5.2 Jumper Function Description

Jumper
1
2
3
4
5
6
Description
UPS Alarm (DB9.P2)
UPS Online Mode, ECO Mode, Inverter Mode (DB9.P8)
Bypass Mode (DB9.P6)
Low Battery (DB9.P7)
Utility Failure (DB9.P9)
UPS Failure (DB9.P1)
To achieve a Normally Closed dry-contact signal, the jumper should
connect the pins 2 and 3.