Cooper Lighting Solutions Portfolio LDA2B Instrucciones De Instalación página 3

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation Instructions – LDA2B/LDSQAB/LDA2BCP/LDSQABCP Commercial Recessed Adjustable LED
Hanger Bar
Adjustment Screws
Figure 3
To Remove Lid, Loosen and
Remove Screws (4x)
Figure 4
WIRING
Ceiling Access Only Fixtures
1.
Remove the outer JBOX cover (driver attached to
cover). Connect supply leads and appropriate dimming/
controls leads as specified in the wiring diagrams
and in accordance with your local electrical code(s) or
N.E.C. (see figure 5a).
Figure 5a.
Below Ceiling Access Fixtures
(D010/D010TR designation)
1.
2.
3.
4.
5.
6.
7 .
Figure 5b.
Remove Driver Door
to Make Connections
Figure 5c.
COOPER LIGHTING SOLUTIONS IB520064ML
All supply wiring must be done INSIDE the housing (not
the JBOX). A minimum of 10in [250mm] of insulated
unshielded supply wire and dimming wire should be
placed neatly inside the housing.
Remove outer JBOX door.
Connect dimming wires and keep a minimum of
10in [250mm] of insulated unshielded wire inside the
housing.
Connect supply wires and keep a minimum of 10in
[250mm] of insulated unshielded wire inside housing.
Supply wires connection should be made inside the
housing and the excess wire be tucked into the corner
of the housing near the JBOX away from the aperture
of the housing.
Replace outer JBOX door.
See figure 5b-5c for visual assistance
Dimming wires to be
placed behind here
Remove JBOX Door
Route wires
through here
Installation instructions
3

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Portfolio ldsqabPortfolio lda2bcpPortfolio ldsqabcp

Tabla de contenido