Inspection And Maintenance Plan - Gude GSE 951 Traducción Del Manual De Instrucciones Original

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 97
ENGLISH
20

Inspection and maintenance plan

Regular servicing period
Petrol hose
Exhaust system
Choke
Cable starter
Air filter
Petrol filter
Spark plug
Tip: To ensure reliable operation of the electric generator, we strongly recommend using fuel additives and
performing 2-3 test operations after a longer time of not using the unit.
Failure removal
Failures 
 
The motor does not start.
Engine running irregu-
larly
Unit not producing any
current.
Engine stopping
Before any
start-up
Inspection
Clean
Change
Clean
Inspection
Clean
Causes
Closed fuel tap
Lack of fuel
Weak tension on the starter
Wrong fuel, storing without petrol tank
being drained
Sooted spark plug (carbon residues on
electrodes), electrodes distance too big
The spark plug is wet from petrol (over-
saturated engine).
Unit is not in a horizontal position. Lack
of oil being signalled
Choke has not been used
Too small appliance
Problem with ignition
Wrong fuel (propellant)
Short circuit
Broken cable
Loose cable
The Starting current is too big.
Too long cable
After 1 month After 3 months
or 50 hours of
operation
9
Removal
Make sure the fuel tap and On/Off are in
the „ON" position
Add some fuel
Pull strongly the starting cord.
Drain the fuel tank and carburettor, add
fresh petrol
Clean the spark plug, check the plug ther-
mal value, possibly change the plug, set the
electrodes distance to 0.6-0.7 mm
Dry the spark plug out and refit it.
Place the unit in a horizontal position
Use the choke
Make sure the spark plug is fitted proper-
ly. Make sure the spark plug cable is on
the spark plug. Clean the spark plug and
check the electrodes if correct.
Make sure proper fuel has been used.
Indicator is off:
An error that you can remove yourself.
Contact the GÜDE service centre.
Indicator is on:
1. Press the overloading protection for
the used output.
2. Check the cables.
3. Check for a short circuit or overloa-
ding.
Reduce the appliance
Shorten the cable
After 6 months
After 12
months
4

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

40726

Tabla de contenido