Water Supply Pump And Water Collection Tank - LU-VE Emeritus Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Water supply pump and water collection tank

The complete Emeritus system and also the versions with only adiabatic panels contain the following two components: water supply
pump and flowmeter.
Pump and flowmeter characteristics:
• Pump
• Water collection tank
Cleaning the water recovery tank
Cleaning the water recovery tank is recommended at the beginning of the season, after the lowering period and at the end of
the season
Cleaning the tank, including the net filter positioned at the inlet of the water that runs off the coil must be carried out with jets
of clean water or water with detergent compatible with the construction materials of the machine
For long periods of inactivity it is absolutely necessary to completely empty the plant; the system can be drained automatically.
Single-phase power supply: 220-240V 50Hz 2-pole
Maximum liquid temperature: 40°C
Insulation class: 130°C (B)
Protection grade: IPX8
Free passage of solids in suspension: 10 mm
Fitted with integrated floats and condensers, thermal motor
protector and device for shallow suction (down to a depth of
3mm).
Pump component materials: Resin PPO+20%GF, PA66+30%GF,
NBR, AISI 304 and 316 stainless steel.
Max static pressure: 11m
Nominal power: 0.55kW
Absorbed current: 3.47A
Supply line diameter: 1 ¼"
The tank is in AISI 304.
Both water collection tank and pump are delivered separately.
The installer is responible for their assembly
16
Max water flow:225 l/min
Absorbed power: 0.78kW
Electric capacitor: 16 µF

Publicidad

Tabla de contenido
loading

Tabla de contenido