Características Técnicas
/ Caracteristicas Tecnicas / Technical Data
Torneira de mesa para Lavatório Zenit DocolTronic - 00045706
Grifo de mesa para lavatório Zenit DocolTronic - 00045706
Basin pillar tap - Zenit DocolTronic - 00045706
Torneira de mesa para Lavatório Zenit DocolEletric
Grifo de mesa para lavatório Zenit DocolEletric
Basin pillar tap - Zenit DocolEletric
Acionamento automático do fluxo de água com a aproximação no campo de detecção
do sensor.
Funcionamento
Accionamiento automatico del flujo de agua con aproximación en el campo de detección del
Funcionamiento
sensor.
Operation
The water flow is activated automatically when the user brings his hands within the sensor's
range.
Tempo de retardo para fechamento da válvula
solenóide
Tiempo de retardo para cerrar la valvula
solenoide
Valve delay time
Tempo máximo de acionamento contínuo
Tiempo maximo de accionamiento continuo
Maximum flush time
Torneira de mesa para Lavatório DocolEletric
Grifo de mesa para lavatório DocolElétric
Basin pillar tap - DocolEletric
Funcionamento
Funcionamiento
Operation
Tempo de retardo para fechamento da válvula
solenóide
Tiempo de retardo para cerrar la valvula
solenoide
Valve delay time
Tempo máximo de acionamento contínuo
Tiempo maximo de accionamiento continuo
Maximum flush time
2
Normal
Pressure / Alta Presión
00464806
2 s
60 s
Acionamento automático do fluxo de água com a aproximação no
campo de detecção do sensor.
Accionamiento automatico del flujo de agua con aproximación en
el campo de detección del sensor.
The water flow is activated automatically when the user brings his
hands within the sensor's range.
2 s
60 s
Maintenance
SYMPTOMS
Faucet does not deliver any water when Sensor
is activated.
Solenoid valve produces an audible "CLICK".
Alta pressão / High
00550306#
Faucet does not deliver any water when
Sensor is activated.
Solenoid valve no produces an audible
"CLICK".
Faucet does not stop delivering water
Low flow
SYMPTOMS
Faucet does not deliver any water when
Sensor is activated.
Solenoid valve produces an audible
"CLICK".
406
#
Faucet does not deliver any water when
Sensor is activated.
Solenoid valve no produces an audible
"CLICK".
Faucet does not stop delivering water
Low flow
DOCOLELETRIC TROUBLESHOOTING GUIDE
POSSIBLE REASONS
Open water supply stop valve
Water supply failure
Open the Inlet Flow
Disassemble and clean the core of Inlet Flow Control Filter.
Inlet Flow Control
Open Inlet Flow Control flow turning clockwise the core.
Inlet Flow Control closed
Verify overload protect
No power
Power cord is not connected in the electrical outlet
Connect power cord to power inlet
Bad connection between sensor and power switch
Connect the cableas again
Faulty Sensor cable
Available at Docol Authorized Distributor in your country
Available at Docol Authorized Distributor in your country
Faulty sensor
Remove the object
Object in recognition range sensor
Connect the solenoid valve cable to sensor cable again
Faulty solenóide valve cable
Inlet Flow Control not enough open
Turn clockwise the core of Inlet Flow Control
Pipe system or core of Inlet Flow Control flow is
Open Inlet Flow Control flow, clean the core
clogged
Open the system pipe in another point let the water and air
Air inside pipe system
go out until only water goes out.
Change the position way flow solenoid valve mounted. Caution
Solenoid valve mounted with opposite way flow
on the signal way flow under the solenoid valve
Water supply stop is partially closed
Completely open water supply stop
Aerator is clogged
Remove, clean, and reinstall aerator
DOCOLTRONIC

TROUBLESHOOTING GUIDE

POSSIBLE REASONS
Open water supply stop
Water supply failure
Open the Inlet Flow Control
Inlet Flow Control
Disassemble and clean the core of Inlet Flow Control Filter
Open Inlet Flow Control flow turning clockwise the core
Inlet Flow Control closed
Batteries low. LED blink red once every 1 second
Replace batteries
Insert the batteries like showed in the figure 2A page 10. Caution
The polarity battery is reversed
in battery polarity
Connection Failure between solenoid valve and
Connect the solenoid valve cable to sensor cable again
sensor.
Faulty Sensor cable
Available at Docol Authorized Distributor in your country
Faulty sensor
Available at Docol Authorized Distributor in your country
Remove the object
Object in recognition range sensor
Faulty solenóide valve cable
Connect the solenoid valve cable to sensor cable again
Inlet Flow Control not enough open
Turn clockwise the core of Inlet Flow Control
Pipe system or core of Inlet Flow Control flow is
Open Inlet Flow Control flow, clean the core
clogged
Open the system pipe in another point let the water and air
Air inside pipe system
go out until only water goes out.
Change the position way flow solenoid valve mounted. Caution
Solenoid valve mounted with opposite way flow
on the signal way flow under the solenoid valve
Water supply stop is partially closed
Completely open water supply stop
Remove, clean, and reinstall aerator
Aerator is clogged
SOLUTIONS
Control.
SOLUTIONS
15