2 Product Feature
2-1. Specification
Source power requirement
Voltage/current of output on the
Transmission Booster side
Environmental condition
Dimensions
Weight
Installation Environment
2-2. Appearance
TB1
Power line terminal
3 Installation
3-1. Parts prepared at site
Please prepare the following parts before installation of the unit.
Preparation parts
Unit fixing screw
Power cable/
Protective earth cable
(Ground cable)
Main power switch
(Circuit breaker)
Transmission cable
*Use a breaker with a contact distance of 3 mm (1/8 in) or more.
4
Rated input
EU: ~220 V - 240 V ; 0.7 A / 50 Hz Single-phase
voltage and current
US: ~208 V - 230 V ; 0.7 A / 60 Hz Single-phase
Fuse: 2.0 A Time-delay type (IEC127-2 S.S.5)
DC28 V - 30 V 1.7 A (Maximum loading)
Temperature
Operating range 0 - 40 °C / 32 - 104 °F
Storage range
Humidity
30 - 90 %RH (No condensation)
340 (H) × 360 (W) × 59.2 (D) mm / 13 7/16 (H) × 14 3/16 (W) × 2 3/8 (D) in
3.5 kg / 7 3/4 lb
In the metal control panel box (indoor)
* This unit is installed and used in a business office or equivalent environment.
Cable fixture
M4 screw × 4 pcs
Use sheathed vinyl cord or wire.
Wire type: Wire should not be lighter than ordinary PVC sheathed flexible cord IEC 60227
(designation 60227 IEC 53)
Wire size: 0.75 mm² to 2 mm² (AWG18 to 14)
Qty.: 1 pc
Type: 250 VAC, Single-phase 3 A
Type of the cable; Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
• CPEVS ø1.2 mm to ø1.6 mm
• CVVS 1.25 mm² to 2 mm² (AWG16 to 14)
* CPEV; PE insulated PVC jacketed shielded communication cable
* CVVS; PVC insulated PVC jacketed shielded control cable
PE: Polyethylene PVC: Polyvinyl chloride
Cable length: Please refer to section "5 Transmission cable length limitation".
-20 - 60 °C / -4 - 140 °F
360 (14 3/16)
240 (9 1/2)
UP
Specification
59.2 (2 3/8)
TB3
M-NET Transmission
terminal block 2
TB2
M-NET Transmission
terminal block 1
Cable fixture
Unit: mm (in)