Haier MRV Serie Instrucciones De Instalación página 17

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ELECTRICAL WIRING
Wire gauge size and breaker size for total indoor amp draw. Current NEC guidelines and local codes will trump this chart.
Items
Total Current
of Indoor
Units (A)
< 7
7 and < 11
11 and < 16
16 and < 22
22 and < 27
• The electrical power line and signal lines must be tightened.
• Every indoor unit must have a ground connection.
• The power wire should be size up if it exceeds the permissible length.
• Shielding of the wire of all the indoor and outdoor units should be connected and grounded at one point in the outdoor
unit. The far end of the shielding wire should be wrapped back and taped.
• Signal lines should not exceed 3280ft (1000m).
Wired Controller ABC Chart
Length of Controller Wire ft ( m)
820 (250)
• The shielding layer of the controller wire must be grounded at the equipment end, and taped back at the terminal end.
• The total length of the controller wire shall not be more than 820ft (250m).
31-5000500 Rev. 0
Cross Section
Length
AWG (mm²)
in (mm)
14 (2.5)
65.6 (20)
12 (4)
65.6 (20)
10 (6)
82 (25)
8 (8)
98.4 (30)
6 (10)
131 (40)
Wiring Dimensions AWG (mm²)
18 (0.75) x 3 core shielding line
Rated Current
Rated Current of
of Overflow
Residual Circuit
Breaker (A)
Breaker (A)
Ground Fault
Interrupter (mA)
Response Time (S)
10
10 A, 30 mA, 0.1S or below
15
15 A, 30 mA, 0.1S or below
20
20 A, 30 mA, 0.1S or below
30
30 A, 30 mA, 0.1S or below
30
30 A, 30 mA, 0.1S or below
Cross
Sectional Area
of Signal Line
16 AWG (1.25mm²)
17

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mvad007mv2aaMvad009mv2aaMvad012mv2aaMvad018mv2aaMvad024mv2aa

Tabla de contenido