Setting the hysteresis
Selecting the hysteresis
Example
The hysteresis can be set between ± 0.2 K, 0.4 K, 0.6 K, 0.8 K and 1 K (factory setting 0.4 K) (K =
Kelvin). If, for example, the hysteresis is 1 K and the room thermostat is set to regulate to a tempera-
ture setpoint of 20°C, the room thermostat switches on at 19°C and switches off again at 20°C.
Personal:
•
Qualified electrician
The jumper can be inserted in two different positions (2-point position and
PID position), depending on which function is desired.
In the factory setting, the jumper is inserted in the PID position. In this posi-
tion, you can set the heating cycle. If the jumper is in the 2-point position,
you can set the hysteresis.