Descargar Imprimir esta página

Cooper Crouse-Hinds Terminator II TMCX Serie Información De Instalación Y Mantenimiento

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

TMCX Terminator
II Cable Fitting
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
TMCX Series Terminator
II Cable Fittings are designed for use with Type MC/MC-HL jacketed metal-clad cable, interlocked armour and continuous corrugated
armour, TECK, ITC, and Type TC tray cable in hazardous (classified) locations when installed, in accordance with NEC/CEC. TMCX Series Terminator II Cable Fittings
are cULus Listed for hazardous locations (with TSC Epoxy Sealing Compound and Chico
Standard C22.2 No. 174. They are suitable for use in NEC/CEC Class I, Divisions 1 & 2, Groups A, B, C, D; Class II, Divisions 1 & 2, Groups E, F, G; and Class III,
when installed in accordance with NEC/CEC.
Explosionproof cable fittings should be installed, inspected, and maintained by qualified and competent personnel.
WARNING
To avoid risk of electrical shock, electrical power must be OFF before and
during installation and maintenance.
Sealing Chamber
Thread Body
CABLE PREPARATION
1.
Remove jacket (and armour, if applicable) from the cable to expose a
sufficient length of conductors required for the job.
For trade sizes 1/2" to 1-1/4" (M20 to M40) with type MC cable, leave
0.92" (23.3mm) of armour exposed when cable O.D. is from mid to upper
range, and 0.82" (21.0mm) when cable O.D. falls at the lower range.
Prepare cable. For Type MC, remove all fillers and shielding back to
armour. For Type TC, remove fillers back to cable jacket. Separate
uninsulated ground conductors back to armour or sheath to allow sealing
of individual strands.
2.
Install TMCX into hub, wrench-tight.
3.
Apply electrical tape to tip of conductors, and slide through integral dam
until armour or TC jacket contacts the dam.
IF 1647 • 07/13
Copyright © 2013, Cooper Industries, Inc.
®
LiquidSeal only) according to UL Standards 514B and 2225, and CSA
Back Nut
Environmental Seal
Dam
Rear Assembly
Union Nut
4.
Tighten back nut wrench-tight and visually inspect that environmental
seal has collapsed 360° around cable jacket. If desired, use included
torque table as a guideline.
CAUTION
To avoid risk of ignition:
1. Tools must not be allowed to damage the tapered flame path surfaces.
Do not handle sealing chambers roughly, or use tools that might damage
or scratch the tapered surfaces.
2. Any excess sealing compound should be removed from the exterior
tapered surface of the sealing chamber immediately.
3. The sealing chamber should be fully bottomed to the rear assembly
before assembly to the thread body.
4. Before reassembly, examine the tapered joint surfaces of the thread
body and sealing chamber. Surfaces must seat fully against each other
to provide a proper explosionproof joint. Remove any dirt or other
foreign matter from both surfaces. If either surface is scratched,
marred, corroded, or otherwise damaged, do not reassemble. Replace
the fitting.
5. After packing sealing chamber with TSC, be sure to allow compound to
harden before moving conductors.
5.
Disassemble union nut and remove rear assembly from thread body.
5a. For Chico
®
LiquidSeal installation: remove electrical tape and separate
conductors. Mix liquid compound per included instructions. Hold cable
gland upright and pour liquid compound until it reaches the top of the
compound chamber. Wiggle and separate conductors to make sure
compound settles between conductors, and top off if necessary. Maintain
assembly in vertical position until compound has gelled. See cure graph
for gel and energizing times.
IF 1647
5b. For TSC installation: (with cables containing more than four (4)
conductors, Chico
®
LiquidSeal is recommended): unscrew and remove
sealing chamber, remove electrical tape, and separate conductors. Mix
two-part epoxy sealing compound provided by kneading and folding until
a uniform color is obtained (approximately 2-3 minutes). Pack a
sufficient amount of compound between and around conductors, using
the length and ID of the sealing chamber as a guide for shaping the
compound. Insert conductors into sealing chamber and slide the sealing
chamber down over the sealing compound. As compound is getting
compressed, use a hardwood stick or dowel to remove excess compound
and prevent it from getting into the mating threads. Screw sealing
chamber into mating thread and pack more sealing compound from the
top of the sealing chamber, making sure conductors are properly sealed
around, and the sealing chamber is completely full. Wipe off any
compound from the sealing chamber's exterior immediately. Allow
compound to sufficiently harden before moving conductors to avoid
creating voids. Allow TSC to cure for 24 hours before energizing
equipment.
Entry
NPT
Thread
Catalog No.
1/2"
TMCX050 1
1/2"
TMCX050 2
3/4"
TMCX075 1
3/4"
TMCX075 2
1"
TMCX100 1
1"
TMCX100 2
1-1/4"
TMCX125 1
*All dimensions in inches; metric millimeters shown in parenthesis.
†When making your cable gland selection based on Cable O.D., be sure to also observe the Over Conductors O.D. dimension.
See pages 7 and 8 for gel time and energize / return to service time graphs.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof
are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine
the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Page 1
6.
Insert the rear assembly into the thread body. Tighten union nut
wrench-tight. Assembly is complete.
Catalog No.
TMCX050 1
TMCX050 2
TMCX075 1
TMCX075 2
TMCX100 1
TMCX100 2
TMCX125 1
SELECTION TABLE
Armour O.D.
Over
Entry Thread
Metric
Conductors O.D.
(MetricOption)
Catalog No.
Max. Inches†
Min.
M20
TMCXM20 1
0.480
0.40 (10.16)
M20
TMCXM20 2
0.480
0.56 (14.22)
M25
TMCXM25 1
0.713
0.40 (10.16)
M25
TMCXM25 2
0.713
0.56 (14.22)
M32
TMCXM32 1
0.939
0.56 (14.22)
M32
TMCXM32 2
0.939
0.78 (19.81)
M40
TMCXM40 1
1.172
0.78 (19.81)
Cooper Crouse-Hinds LLC
PO Box 4999, Syracuse, New York 13221 • USA
Copyright © 2013, Cooper Industries
TORQUE TABLE
Torque in.-lb. (N-m)
800 (90)
800 (90)
800 (90)
800 (90)
1000 (113)
1000 (113)
1000 (113)
Cable O.D.
Max.
Min.
Max.
0.86 (21.84)
0.49 (12.45)
0.90 (22.86)
1.14 (28.96)
0.65 (16.51)
1.18 (29.97)
0.86 (21.84)
0.49 (12.45)
0.90 (22.86)
1.14 (28.96)
0.65 (16.51)
1.18 (29.97)
1.14 (28.96)
0.65 (16.51)
1.18 (29.97)
1.35 (34.29)
0.87 (22.10)
1.39 (35.31)
1.35 (34.29)
0.87 (22.10)
1.39 (35.31)
IF 1647
Revision 2
Revised 07/13
Supercedes 05/13

Publicidad

loading

Resumen de contenidos para Cooper Crouse-Hinds Terminator II TMCX Serie

  • Página 1 Maintain are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine assembly in vertical position until compound has gelled. See cure graph the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
  • Página 2 Mélanger le composé liquide selon les instructions incluses. des essais que nous estimons fiables. Nous ne pouvons toutefois en garantir ni la précision ni l’exhaustivité. Conformément conditions de vente de Cooper Crouse-Hinds, et étant Saisir l’écrou du câble pour le tenir à la verticale et verser du ciment liquide pour donné...
  • Página 3 Inserte el montaje posterior al cuerpo de la rosca. Ajuste la tuerca de Empalme de cable TMCX Terminator ™ unión con llave. El montaje está terminado. Información de Instalación y Mantenimiento IF 1647 GUARDE ESTAS INSTRUCCIONES PARA REFERENCIA FUTURA APLICACIÓN Los empalmes de cable TMCX Series Terminator™...
  • Página 4 Todas las afirmaciones, recomendaciones y datos técnicos incluidos en este manual se basan en información y pruebas que consideramos confiables. No se garantiza que los datos sean exactos ni completos. De acuerdo con las “Condiciones de venta” de Cooper Crouse-Hinds y debido a que las condiciones de uso están más allá de nuestro control, el comprador debe determinar si el producto es adecuado para el uso previsto y asumir la totalidad del riesgo y la responsabilidad relacionados con el mismo.

Este manual también es adecuado para:

Tmcx050 1Tmcx050 2Tmcx075 1Tmcx075 2Tmcx0100 1Tmcx0100 2 ... Mostrar todo