INSTALLATION INSTRUCTIONS
FOR THE M201EA OUTPUT MODULE
This manual is intended as a quick reference installation guide. Please refer to the
control panel manufacturers installation manual for detailed system information.
The M200 series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices. The M201EA
is an output module that allows the control of auxiliary devices such as fire shutters
or sounders.
A single tri-colour LED indicates the status of the module. In normal conditions, the
LED can be set by command from the control panel to blink green when the module is
polled. When the control panel switches the relay to the energised state the LED can
be set to continuous green.
SPECIFICATIONS
Operating Voltage Range:
Maximum Standby Current
LED Current (Red):
LED Current (Yellow):
Isolator features:
Humidity:
Maximum Wire Gauge
INSTALLATION
Note: These modules must only be connected to control panels using compatible
proprietary analogue addressable communication protocols for monitoring and control.
M200 series modules can be mounted in several ways (See Figure 1):
1:1 An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132 mm (H) x 137 mm
(W) x 40 mm (D)
1:2 The DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm "Top Hat"
DIN rail inside a control panel or other suitable enclosure. Push module into adaptor
bracket until it clips into place. Locate top clip over DIN rail and rotate bottom down
to clip into place. To remove, lift up, then rotate top away from the rail.
Wiring to all series M200 modules is via plug in type terminals capable of supporting
conductors up to 2.5 mm²
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches (see
Figure 4). A screwdriver should be used to rotate the wheels to select the desired
address, either from the front or the top of the module. (Note: The number of addresses
available will be dependent on panel capability, check the panel documentation for
information on this.)
Short Circuit Isolators
All M200 series modules are provided with short circuit monitoring and isolators on the
intelligent loop. If required the isolators may be wired out of the loop to facilitate the
use of the modules on high current loaded loops, for example if sounders are used.
To achieve this, the loop out positive should be wired to terminal 5 rather than terminal
2. See the relevant wiring diagram for details.
M201EA WIRING
The M201EA can be wired for either Supervised (Figure 2) or Non-Supervised
(Figure 3) operation respectively.
Observe precautions when handling and making connections
M201EA Single Output Module with Supervised Output
When the module is used in supervised mode and power is supplied to the module,
a switched negative input on terminal 12 can be used to signal an external fault
condition, such as a power supply fault. Loss of power is also supervised in this mode
(ii)
such that if the supply voltage falls below 7V a fault indication is achievable. Note that
the use of this fault mode is dependant on panel software. Please contact the panel
manufacturer for further details.
PSU monitoring is not available when the module switches the output to Alarm.
Wire as follows (see Figure 2):
a: T1 Loop Output -. b: T2 Loop Output +. c: T3 Loop Input -. d: T4 Loop Input +
e: T5 Loop Output +. If short circuit isolation is not required, loop output+ should be
wired to terminal 5 and not 2. Terminal 5 is internally connected to terminal 4.
f: To enable output circuit supervision, the link supplied must be fitted across
terminals 6 and 7, and the load must be polarised.
15 to 32VDC (Min 16.5VDC for LED operation)
160 µA - No Communication
1.5 mA
5.5 mA
see S00-7100
5% to 95% relative humidity (non-condensing)
2.5 mm²
CAUTION
CAUTION
Electrostatic Sensitive Device
I56-4401-000

Publicidad

loading

Resumen de contenidos para System Sensor M201EA

  • Página 1 To achieve this, the loop out positive should be wired to terminal 5 rather than terminal 2. See the relevant wiring diagram for details. M201EA WIRING The M201EA can be wired for either Supervised (Figure 2) or Non-Supervised (Figure 3) operation respectively. CAUTION...
  • Página 2 10 and 11 to ensure it does È possibile cablare il modello M201EA affinché funzioni in modalità di Supervisione not drop below 7V, and also monitors for a switched negative fault signal from (Figura 2) o di Non Supervisione (Figura 3).
  • Página 3 5 en vez de al terminal 2. Si desea información más detallada, consulte los diagramas de conexión correspondientes. CONEXIONES DEL M201EA El M201EA se puede conectar para que funcione Con Supervisión (Figura 2) o Sin Supervisión (Figura 3). PRECAUCIÓN Equipo sensible a la electricidad estática...
  • Página 4 Ausgang "Ringleitung+" direkt an Klemme 5 und nicht an Klemme 2 angeschlossen werden. M201EA Verdrahtung Das Modul M201EA kann für den überwachten (Abbildung 2) oder nicht überwachten (Abbildung 3) Betrieb verdrahtet werden. ACHTUNG Elektrostatisch empfindliches Gerat Beachten Sie die Vorschriften fur den Umgang mit elektrostatisch empfindlichen Geraten M201EA Steuermodul mit Einem Überwachbarem Ausgang...