SPECIFICATIONS
PHYSICAL SPECS
SIZE: 2.74"H x 1.68"W x 1.63"D (6.96 cm x 4.27 cm x 4.14 cm)
(not including ground strap)
WEIGHT: 5 oz
MOUNTING: Single Gang Switch Box
MOUNTING HEIGHT: 30-48 in (76.2-121.9 cm)
SILICONE FREE
ROHS COMPLIANT
ELECTRICAL SPECS
MAXIMUM LOAD (Single Phase)
800 W @ 120 VAC
1200 W @ 277 VAC
1500 W @ 347 VAC
COVERAGE PATTERN
• Small motion (e.g. hand movements) detection up to 20 ft (6.10 m), ~625 ft
• Large motion (e.g. walking) detection greater than 36 ft (10.97 m), ~2025 ft
• Wall-to-wall PIR coverage
• Units with -PDT (Passive Dual Technology) option
(also called Microphonics) provide overlapping
detection of human activity over the complete
PIR coverage area. Advanced filtering is utilized
to prevent non-occupant noises from keeping
the lights on.
CONVERSION FROM GROUND ONLY (NO NEUTRAL) TO NEUTRAL WIRING
This product is pre-configured for wiring without a neutral; however, if connection to neutral is required by code, the unit easily converts in seconds.
Step 1:
Remove Yellow
Label
WIRING TO GROUND (NO NEUTRAL)
H
GND
BLK
BLK
PARALLEL (3-WAY)
H
N
GND
LOAD
BLK
BLK
Sensor Switch 900 Northrop Road, Wallingford, CT 06492 Phone: 1.800.PASSIVE sensorswitch.com ©2014 Acuity Brands Lighting, Inc. All rights reserved 01/26/14
IS-WSX-004
WSX
INSTRUCTIONS
MINIMUM LOAD: None
MOTOR LOAD: 1/4 HP
FREQUENCY: 50/60 Hz (timers are 1.2x for 50 Hz)
ENVIRONMENTAL SPECS
OPERATING TEMP
Standard: 14º to 122º F (-10º to 50º C)
LT Option (PIR): -40º to 122º F (-40º to 50º C)
LT Option (PDT): -4º to 122º F (-20º to 50º C)
RELATIVE HUMIDITY:
Standard: 20 to 75% non-condensing
LT Option: 20 to 90% non-condensing
(electronics coated for corrosion resistance)
SIDE VIEW
SIDE VIEW
1.2 m
1.2 m
4 ft
4 ft
0
m
3
6
m
0
3
0
ft
9
18
ft
0
9
Small motion
Small motion
detection to ~20 ft
detection to ~20 ft
Large motion detection to >36 ft
Large motion detection to >36 ft
Step 2:
Loosen Screws and
Remove Metal Link
WIRE COLOR KEY
120/277 VAC WIRING
BLACK*
N
BLACK*
347 VAC WIRING (-347 Option)
Red wires replace Black wires.
LOAD
For additional wiring diagrams, scan QR CODE below or go to:
http://bit.ly/12HaeEF
GND
NOTE: When wiring in parallel, both
BLK
units must time out for lights to
BLK
turn off. Disabling switch function is
recommended (Function 4, Setting 2).
FAMILY
BASE MODEL #s
WSX: Passive Infrared (PIR) Detection - Auto On
WSX SA: Passive Infrared (PIR) Detection - Manual On
WSX NL: Passive Infrared (PIR) Detection - Manual On
WSX PDT: Dual Technology (PIR + Microphonics) Detection - Auto On
WSX PDT SA: Dual Technology (PIR + Microphonics) Detection - Manual On
WSX PDT NL: Dual Technology (PIR + Microphonics) Detection - Manual On
20
6
Small
Small
20
6
motion
motion
detection
detection
to ~20 ft
2
2
10
3
10
3
9
12
6
9
12
0 ft
12
0 m
9
6
0 ft
0 m
12
9
27
36
18
27
36
36
30
20
36
30
Step 3:
Connect Neutral to
Silver Screw and
Ground to Green Screw
WIRING TO NEUTRAL
}
*BLACK wires
- Line Input
- Load Output
can be reversed
TOP VIEW
Small
Small
motion
motion
detection
detection
to ~20 ft
3
0 m
3
6
3
0 m
10
0 ft
10
20
10
0 ft
Small motion ~40 ft coverage
Small motion ~40 ft coverage
N
H
GND
BLK
BLK
PARALLEL (3-WAY)
N
H
N
GND
LOAD
BLK
BLK
BLK
BLK
TOP VIEW
TOP VIEW
6
9
12
3
6
9
1
20
30
36
10
20
30
N
LOAD
N
GND
1 of 2