DIRECT SOCKET INSTALLATION
REGULAR SOCKET ENDS
*
*
THIS SIDE UP
Solvent Cement Welded Socket
Joint
PRECAUTIONS AND WARNINGS
CAUTION: The system must be designed and installed so as not to pull the
components in any direction. Pipe system must be cut and installed in such
a manner as to avoid all stress loads associated with bending, pulling, or
shifting. All piping systems must be supported.
CAUTION: BEFORE THE VALVE IS CYCLED, all dirt, sand grit or other
material shall be fl ushed from the system. This is to prevent scarring of
internal components.
WARNING: System should not be operated or fl ushed out at fl ow velocities
greater than 5 feet per second.
NOT FOR USE WITH COMPRESSED AIR OR GAS
WARNING: Do not use compressed air or gas to test any PVC or CPVC
thermoplastic piping product or system, and do not use devices propelled
by compressed air or gas to clear the systems. These practices may result
in explosive fragmentation of system piping and components causing bodily
injury or death.
All air must be bled from the system during the initial fl uid fi ll. Pressure testing
of the system must not be made until all solvent cement joints have properly
cured. Initial pressure testing must be made at approximately 10% of the
system hydrostatic pressure rating to identify potential problems prior to
testing at higher pressures.