Troubleshooting
Lights will not turn on:
LED does not flashe:
Check all wire connections and verify the ground wire
is tightly secured.
LED does flashe:
Check all wire connections and verify the load wire is
tightly secured.
Check light level photocontrol setting. Cover the
sensor lens to simulate darkness in the room. If the
lights come ON, the light level needs to be adjusted.
If set for minimum, more than 10 Fc of ambient light
will cause the lights to be held OFF . See Sensor
Adjustment section for instructions.

Wiring Diagram

Neutral
(White)
Line (Black)
Load (Red)
Occupancy
Sensor
Figure 4.
Installation Instructions - Quadcast LED Occupancy Sensor (QDOCC)
Factory Wired AC
Input to Driver
Neutral (White)
Line (Black)
Factory Wired AC
Input to Driver
Neutral
(White)
Neutral
(White)
Line (Black)
Line (Black)
Lights will not turn off:
The time delay can be set from a minimum of 30 seconds
(fully counter-clockwise) to a maximum of 30 minutes (fully
clockwise). Ensure that the time delay is set to the desired
delay and that there is no movement within the sensor's
view for that time period.
To quickly test the unit for proper operation, turn the time
delay to minimum and move out of the sensor's view.
Lights should turn OFF after 30 seconds.
Operation during power-up
During the sensor warm-up period, which can last up to
a minute after initial power-up (or after a lengthy power
outage), the load can be either ON or OFF , depending on
the status of the relay before the sensor was powered
down. After warm-up, the sensor will open or close the
relay to correspond to the occupancy status of the room.
Quadcast without
Occupancy Sensor
Quadcast with
Occupancy Sensor
Neutral (White)
Line (Black)
Load (Red)
EATON
IB515004EN
Red
LED Driver
Black
Factory Wired
Driver to LEDs
Red
LED Driver
Black
Factory Wired
Driver to LEDs
Installation instructions